Siemens LMV5 Series Technical Instructions page 29

Linkageless burner management system
Hide thumbs Also See for LMV5 Series:
Table of Contents

Advertisement

LMV Series
Technical Instructions
Document No. LV5-1000
AZL5 Display
The AZL5 is designed to be mounted in a rectangular cutout through the face / door of an
electrical enclosure. It has one screw on the top and another on the bottom that engage small
plastic tabs which will swing out when the screw is tightened clockwise; the screw can be
loosened to retract the tab and increase clearance before tightening. The tab will pinch the
sheet metal of the enclosure door between itself and the AZL5 gasket. This facilitates easy
removal and replacement of the AZL5 since it is designed to be taken out of the enclosure face
and held in the hands for setup and commissioning.
The AZL5 connects (via the CANbus port on its bottom end) to the LMV5 at terminal X50 with
CANbus cable AGG5.635. The 9-pin CANbus connector requires a clearance of approximately
2.5" below the bottom of the AZL5 on the inside of the door of the enclosure.