Transferring Parameter Sets Using The Azl Display - Siemens LMV5 Series Technical Instructions

Linkageless burner management system
Hide thumbs Also See for LMV5 Series:
Table of Contents

Advertisement

Technical Instructions 
Document No. LV5‐1000 
 
13. At  this  point,  all  other  LMV5  parameters  under  the  "BurnerControl"  and  "RatioControl" 
headings should be reviewed and set accordingly for the individual burner requirements. 
 
Params & Display > BurnerControl 
Params & Display > RatioControl 
 
Section  3  of  this  literature  explains  every  parameter  in  detail,  and  the  most  commonly  used 
parameters are shaded for easy reference. 
 
14. If the burner has a Variable Speed Drive (VSD) on the blower, it must be standardized.  In most 
cases,  the  VSD  is  a  Variable  Frequency  Drive  (VFD).    See  Section  5  in  this  literature  if  the  VFD 
parameters are not already set, and for a more detailed standardization procedure.  If the VFD 
parameters are set, standardize the VFD using the following menu path: 
 
Params & Display > VSD Module > Configuration > Speed 
 
Once Standardization is set to "activated", the air damper should open to its pre‐purge position, 
and the blower should ramp up, pause, and then ramp back down.  If this does not occur, make 
sure that the VSD is set to "air influenced" and the safety loop is closed. 
 
Transferring Parameter Sets Using the AZL Display 
 
This procedure will detail how to transfer a parameter set from one burner to another burner. In this 
example,  the  parameter  set  will  originate  from  Burner  #1  (B1)  and  will  be  copied  to  Burner  #2  (B2).  
Naturally, using a similar procedure, the parameter set from Burner #1 can be copied to Burners #3, #4, 
#5, etc. The ACS450 PC software can also be used for this purpose (see Section 9). 
 
Note:    Passwords  are  transferred  with  the  parameter  sets.    Manual  operation  settings  are  not 
transferred with parameter sets. 
 
1. Obtain the OEM or service level passwords for B1 and B2. 
 
2. On B1, upload all of the current parameters from the LMV5 to the AZL flash memory using the 
following menu path: 
 
Updating > ParamBackup > LMV5x ‐> AZL 
 
The OEM or service level password for B1 will be necessary to access this. This will upload all of 
the current LMV5 parameters to the AZL flash memory. This process is complete when the AZL 
states "Parameters have been stored". If the LMV5 on B2 is known to have a blank burner ID, 
then power off B1 LMV5, remove the AZL, and skip to step 5.  Otherwise, go to the next step. 
 
3. Write down B1 burner ID.  This can be found at the following menu path: 
 
Operation > Burner ID 
 
After this step, B1 LMV5 can be powered off.  After B1 is powered off, remove the AZL. 
 
Section 4 
 
Page 14 
HOME
LMV Series 
SCC Inc. 

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Lmv51.140c1Lmv51.040c1Lmv52.240b1Lmv52.440b1

Table of Contents