6. Monitor the speed of the blower motor during the standardization process.  After 
standardization is activated, the real time speed can be read using the following menu path: 
 
 
 
Params & Display > VSD Module > Speed > Absolute Speed 
 
 
During standardization, the absolute speed should rise up to a peak value and hold steady 
at that value for a few seconds.  Then, the value should drop back down to zero (or near 
zero).   
 
 
The peak value that is seen should be recorded as the standardized speed.  If this doesn't 
happen, it's likely that there's a problem with the VSD or the speed sensor. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 