NOTE:  Depending on the direction of rotation, home position set in the LMV5, and whether the 
actuator is activated or deactivated, the actuator  may rotate as soon as it is addressed.  For this 
reason it is highly recommended  that the actuator shaft be uncoupled from the valve  / damper 
until the parameters pertaining to the above are set, and the initial LMV5 alarm is reset. 
 
5. Address the actuators.  This is accomplished by the following steps: 
 
a. Remove  the  outer  black  cover  of  all  actuators  to  be  addressed.    This  is  done  by 
loosening  the  three  Philips  (Pozidriv)  head  screws  on  the  cover  and  setting  the  cover 
aside. 
 
b. On the AZL, the menu path will be: 
 
Params & Display > Actuators > Addressing 
 
Note that when the "Params & Display" menu is entered, it may be necessary to enter 
the OEM or service level password. 
 
c. Select  the  actuator  to  be  addressed.    When  prompted,  press  the  "Enter"  key  to  begin 
the addressing assignment. 
 
d. Press  the  red  button  on  the  appropriate  actuator.    If  done  correctly,  the  AZL  should 
state that the address assignment was successful. 
 
e. Repeat the procedure above for the other actuators. 
 
f.
The  jumper  must  be  set  to  "Bus  termination"  on  the  last  device  on  the  CANbus  daisy 
chain.  The last device could be an actuator or a PLL module. 
 
g. After all actuators are successfully addressed, the outer black covers can be reinstalled. 
 
 
 
 
 
 
 
 
 
 
 
 
SCC Inc. 
 
 
 
 
 
Figure 4‐3:  Actuator with Cover Removed 
 
Page 11 
HOME
Technical Instructions 
Document No. LV5‐1000 
Section 4 

Hide quick links: