If possible, shut off the burner switch.  Let the burner get back to Phase 12 (standby). 
1.
 
Access the cold start parameters through the following menu path: 
2.
 
Params & Display > LoadController > ColdStart 
 
Set parameter ThresholdOn to the minimum permissible temperature where the burner can be 
released  to  modulate.    Below  this  temperature,  cold  start  will  engage  on  initial  startup  (not 
during  normal  operation).    Set  ThresholdOff  to  a  temperature  higher  than  ThresholdOn.  If 
already  engaged,  cold  start  will  disengage  at  the  ThresholdOff  temperature.    Setting 
ThresholdOn and ThresholdOff is required for cold start. 
 
NOTE:  Parameters  ThresholdOn  and  ThresholdOff  are  percentages  based  on  the  current 
setpoint  (W1).    If  an  additional  temperature  sensor  is  used  on  a  steam  boiler,  ThresholdOn 
and ThresholdOff will be based on parameter Setp AddSensor. 
 
For  a  steam  boiler  that  is  on  a  common  header  with  other  steam  boilers,  an  additional 
3.
temperature sensor is required for cold start. This will typically be a Pt1000 or Ni1000 RTD wired 
to terminal X60.  Pt100 is  possible but  not recommended.  Choose the appropriate sensor via 
parameter AdditionalSens.  
 
There are four basic ways that the cold start can be set.  These are:  
4.
 
a. Basic Low Fire Hold 
The  LMV5  will  be  held  at  low  fire  until  the  ThresholdOff  temperature  is  reached,  and 
then  the  LMV5  will  be  released  to  modulate.  This  "hold"  will  re‐engage  when  the 
temperature falls below the ThresholdOn value.  Parameter StageLoad must be set to 0. 
 
b. Temperature‐based Stepping Start 
The  LMV5  will  be  held  at  low  fire  until  a  certain  temperature  change  is  detected,  and 
then  a  step  up  in  burner  output  (load)  will  be  taken.  This  continues  until  the 
ThresholdOff temperature is reached.  This will achieve the ThresholdOff temperature 
faster than a basic low fire hold.  Parameter StageLoad must be set to a value greater 
than  0,  since  the  step‐up  in  load  is  determined  by  this  parameter.    Parameter 
StageSetp_Mod must also be set to determine the amount of temperature change that 
will trigger a step‐up in load.  Parameter MaxTmeMod should be set to a high number 
(30 min) so that it has no effect. 
 
c. Time‐based Stepping Start  
The LMV5 will be held at low fire until a certain time elapses, and then a step‐up in load 
will be taken.  This continues until the ThresholdOff value is reached.  StageLoad must 
be  set  to  a  value  greater  than  0,  since  the  step‐up  in  load  is  determined  by  this 
parameter.  Parameter StageSetp_Mod should be set to a high number (80%) so that it 
has  no  effect.    Parameter  MaxTmeMod  is  set  to  determine  how  much  time  should 
elapse before the next load step is triggered. 
 
 