2 Engineering
2.3.5

Download the IO-Link configuration to the CPU

1. Open "Devices & networks" from the project tree.
2. Open the "Device view" of the ET 200SP by selecting the ET 200SP and
double-clicking.
3. Select the IO-Link master "CM 4xIO-Link" and open the S7 Port Configuration
Tool by right-clicking "Start device tool..." > "Start".
4. If you are asked for an interface, select the interface where you can reach the
CPU and the ET 200SP.
5. Select the IO-Link master "CM 4xIO-Link" on the left side of the screen and
load the configuration > "Load with devices" by right-clicking
6. After successful loading, you can close S7-PCT again.
2.4

Operation

The following table demonstrates the mode of operation: To test the full
functionality, you need to connect to the CPU online and observe the "MainSafety".
Table 2-10
Step no.
1
2
3
4
Inductive clocking sensor
Entry ID: 109818998,
V1.0,
Action
Set the CPU to RUN.
Attenuate sensor
Actuate acknowledgment
Do not attenuate sensor
05/2023
Result/reaction
CPU starts up
"InductiveClocking" block outputs no
"Enable" signal
"InductiveClocking" block outputs
"AckReq" signal
Acknowledgment LED lit
"InductiveClocking" block outputs
"Enable" signal
"InductiveClocking" block outputs no
"AckReq" signal
Acknowledgment LED goes out
"InductiveClocking" block outputs no
"Enable" signal
22