2 Engineering
2.3.5
Download the IO-Link configuration to the CPU
1. Open "Devices & networks" from the project tree.
2. Open the "Device view" of the ET 200SP by selecting the ET 200SP and
double-clicking.
3. Select the IO-Link master "CM 4xIO-Link" and open the S7 Port Configuration
Tool by right-clicking "Start device tool..." > "Start".
4. If you are asked for an interface, select the interface where you can reach the
CPU and the ET 200SP.
5. Select the IO-Link master "CM 4xIO-Link" on the left side of the screen and
load the configuration > "Load with devices" by right-clicking
6. After successful loading, you can close S7-PCT again.
2.4
Operation
The following table demonstrates the mode of operation: To test the full
functionality, you need to connect to the CPU online and observe the "MainSafety".
Table 2-10
Step no.
1
2
3
4
Inductive clocking sensor
Entry ID: 109818998,
V1.0,
Action
Set the CPU to RUN.
Attenuate sensor
Actuate acknowledgment
Do not attenuate sensor
05/2023
Result/reaction
•
CPU starts up
•
"InductiveClocking" block outputs no
"Enable" signal
•
"InductiveClocking" block outputs
"AckReq" signal
•
Acknowledgment LED lit
•
"InductiveClocking" block outputs
"Enable" signal
•
"InductiveClocking" block outputs no
"AckReq" signal
•
Acknowledgment LED goes out
•
"InductiveClocking" block outputs no
"Enable" signal
22