Figure 27 : Standard Interface Card Configuration Link

4. Set the 'new' IP address of the interface card, as per the configuration sheet.
5. If required, a 'Username' and 'Password' may be set. This will be indicated on the
configuration sheet. However, it is generally recommended that username and
password are kept blank.
6. Ensure the interface card is configured to set inputs to permanent detect if link to
Wimag access point timeouts. Ensure the 'Activate error output' and 'Activate
detection zone outputs' boxes are ticked, and ensure the 'Timeout' value is set to
3000 (30s).
7. Set any other settings of the interface card as per the configuration sheet. Any
deviations from the configuration sheet should be recorded on said sheet.