9 - ELECTRICAL DATA, 30RQS AND 30RQSY UNITS

9.1 - Short-circuit stability current (TN system
30RQS/RQSY
Value with unspecified upstream protection
Short-term current at 1 s - Icw - kA rms
Admissible peak current - Ipk - kA pk
Max. value with upstream protection (circuit breaker)
Conditional short-circuit current Icc - kA rms
Schneider circuit breaker - Compact series
Reference number
(2)
(1)  Earthing system type
(2)  If  another  current  limitation  protection  system  is  used,  its  time-current  and  thermal  constraint  (I²t)  trip  characteristics  must  be  at  least  equivalent  to  those  of  the 
recommended Schneider circuit breaker.
The short-circuit stability current values above are suitable with the TN system.

9.2 - Electrical data, hydraulic module

The pumps that are factory-installed in these units comply with the European Ecodesign directive ErP. The additional electrical
data required
(1)
is as follows:
Motors of single and dual low-pressure pumps (OPTIONS 116T, 116U)
No.
(2)
Description
(3)
1
Nominal efficiency at full load and nominal voltage
1
Nominal efficiency at 75% rated load and nominal voltage
1
Nominal efficiency at 50% rated load and nominal voltage
2
Efficiency level
3
Year of manufacture
Manufacturer's name and trademark, commercial 
4
registration number and place of manufacturer
5
Product's model number
6
Number of motor poles
Rated shaft power output at full load and nominal voltage 
7-1
(400 V)
7-2 Maximum power input (400 V)
8
Rated input frequency 
9-1 Rated voltage
9-2 Maximum current drawn (400 V)†
10 Rated speed
11
Product disassembly, recycling or disposal at end of life 
12 Operating conditions for which the motor is specifically designed
I 
- Altitudes above sea level
II  
- Ambient air temperature
IV  
- Maximum air temperature
V  
- Potentially explosive atmospheres
(1)  Required by regulation 640/2009 with regard to the application of directive 2009/125/EC on the eco-design requirements for electric motors
(2)  Item number imposed by regulation 640/2009, annex I2b.
(3)  Description given by regulation 640/2009, annex I2b.
(4)  To obtain the maximum power input for a unit with hydraulic module add the maximum unit power input from the electrical data table to the pump power input.
† 
To obtain the maximum unit operating current draw for a unit with hydraulic module add the maximum unit current draw from the electrical data table to the pump current 
draw.
††  Above 1000 m, a degradation of 3% for each 500 m should be taken into consideration.
039
045
050
3.36
3.36
3.36
20
20
20
40
40
40
NS100H NS100H NS100H NS100H NS100H NS100H NS100H NS100H NS160H NS160H NS250H NS250H
29670
29670
29670
(4)
)
(1)
060
070
078
3.36
3.36
3.36
3.36
20
20
15
15
40
40
40
40
29670
29670
29670
29670
039
045
050
060
%
81,1 81,1 81,1 81,1 81,1 81,1 81,1 81,1 83,4 83,4 84,8 84,8
%
80,8 80,8 80,8 80,8 80,8 80,8 80,8 80,8 81,2 81,2 82,2 82,2
%
77,5 77,5 77,5 77,5 77,5 77,5 77,5 77,5 78,3 78,3
This information varies depending on the manufacturer and model at the 
time of incorporation. Please refer to the motor name plates.
2
2
2
2
kW
0,8
0,8
0,8
0,8
kW
1,1
1,1
1,1
1,1
Hz
50
50
50
50
V
A
2,1
2,1
2,1
2,1
rpm
2850 2850 2850 2850 2850 2850 2850 2850 2890 2890 2870 2870
r/s
47
47
47
47
Disassembly using standard tools. Disposal and recycling using an 
m
°C
Please refer to the operating conditions given in this manual or in the 
°C
specific conditions in the Carrier selection programs.
080
090
100
120
5.62
5.62
5.62
20
20
15
40
40
40
29670
30670
30670
30RQS/RQSY
070
078
080
090
100
IE3
2
2
2
2
2
0,8
0,8
0,8
0,8
1,3
1,1
1,1
1,1
1,1
1,6
50
50
50
50
50
3 x 400 
2,1
2,1
2,1
2,1
2,9
47
47
47
47
48
appropriate company.
< 1000††
< 55
Non-ATEX environment
140
160
5.62
5.62
20
15
30
30
31671
31671
120
140
160
79
79
2
2
2
1,3
1,7
1,7
1,6
2,4
2,4
50
50
50
2,9
4,2
4,2
48
48
48
27