15 - MAJOR SYSTEM COMPONENTS
According to the Regulation No. 640/2009 and amendment 4/2014 implementing Directive 2005/32/EC with regard to
ecodesign requirements for electric motors.
Product/option
Motor type
Number of poles
Nominal input frequency
Nominal voltage
Number of phases
Motor included in the application domain of the regulation
640/2009 and amendment 4/2014
Sales leaflet for exemption
Ambient air temperature for which the motor is
specifically designed
(1) Only for sizes 039-050 and 080-120
(2) Only for sizes 060-078 and 140-160
15.8 - Water evaporator/condenser
The evaporator/condenser is a plate heat exchanger with one or
two refrigerant circuits. The water connection of the heat exchanger
is a Victaulic connection. It has a thermal insulation of 19 mm thick
polyurethane foam and includes frost protection, as standard.
The products that may be added for thermal insulation of the
containers during the water piping connection procedure must be
chemically neutral in relation to the materials and coatings to which
they are applied. This is also the case for the products originally
supplied by Carrier SCS.
NOTES - Monitoring during operation:
• Follow the regulations on monitoring pressurised
equipment.
• It is normally required that the user or operator sets up
and maintains a monitoring and maintenance file.
• If there are no regulations or to complement them follow
the control programmes of EN 378.
• If they exist follow local professional recommendations.
• Regularly check for possible presence of impurities
(e.g. silica grains) in the heat exchange fluids. These
impurities maybe the cause of the wear or corrosion
by puncture.
• The reports of periodical checks by the user or operator
must be included in the supervision and maintenance
file.
30RQS standard
(1)
or
with option 15LS
Dual-speed
asynchronous
8
Hz
50
V
400
3
No
Article 2.1
°C
68.5
15.9 - Refrigerant
30RQS/RQSY units operate with refrigerant R-410A.
15.10 - High-pressure safety switch
30RQS/RQSY units are equipped with automatically reset safety
pressure switches on the high-pressure side. For the alarm
acknowledgements refer to the 30RB/RQ Touch Pilot Junior control
manual).
15.11 - Storage tank
30RQS/RQSY units are equipped with mechanically welded
storage tanks that permit storing the excess charge when the unit
operates in heating mode.
15.12 - Four-way valve
This permits reversal of the cycle for operation in cooling and
heating mode and during defrost cycles.
15.13 - Control box
The control box of the 30rqs/rqsy units is equipped with electric
heaters to prevent condensation during operation at low outside
temperatures. they are installed on the top of the control box on
the outside, and are covered by a thermal insulation layer. these
heaters are switched on, based on the outside temperature.
30RQSY standard or
30RQS standard
30RQS standard with
(2)
Dual-speed
Asynchronous
asynchronous
6
50
400
3
No
Article 2.1
68.5
option 42
6
60
400
3
No
Article 2.1
68.5
45