Carrier AquaSnap Touch Pilot Junior Series Installation, Operation And Maintenance Instructions
Carrier AquaSnap Touch Pilot Junior Series Installation, Operation And Maintenance Instructions

Carrier AquaSnap Touch Pilot Junior Series Installation, Operation And Maintenance Instructions

Reversible air-to-water heat pumps
Table of Contents

Advertisement

Quick Links

Touch Pilot Junior
I N S TA L L AT I O N ,
O P E R AT I O N
A N D
M A I N T E N A N C E
I N S T R U C T I O N S
30RQSY
30RQS
For the operation of the control please refer to the
Touch Pilot Junior Control manual for the 30RBS/RQS 039-160 series
Reversible Air-to-Water Heat Pumps
30RQS/30RQSY 039-160 "B"
Nominal cooling capacity 30RQS 38-148 kW - 50 Hz
Nominal heating capacity 30RQS 42-150 kW - 50Hz
Nominal cooling capacity 30RQSY 37-146 kW - 50 Hz
Nominal heating capacity 30RQSY 42-151 kW - 50Hz
Original document

Advertisement

Table of Contents
loading

Summary of Contents for Carrier AquaSnap Touch Pilot Junior Series

  • Page 1 Touch Pilot Junior I N S TA L L AT I O N , O P E R AT I O N A N D M A I N T E N A N C E I N S T R U C T I O N S 30RQSY 30RQS For the operation of the control please refer to the...
  • Page 2: Table Of Contents

    CONTENTS 1 - INTRODUCTION .................................... 4 1.1  -  Specific aspects for 30RQSY units with variable available pressure  ..................4 1.2  -  Check equipment received ................................ 4 1.3  -  Installation safety considerations .............................. 4 1.4  -  Equipment and components under pressure ..........................6 1.5  -  Maintenance safety considerations ............................6 1.6  -  Repair safety considerations ..............................7 2 - MOVING AND SITING THE UNIT ..............................9 2.1 ...
  • Page 3 CONTENTS 13 - NOMINAL SYSTEM WATER FLOW CONTROL ........................38 13.1  -  Units without hydraulic module.............................. 38 13.2  -  Units with hydraulic module and fixed-speed pump  ......................38 13.3  -  Units with hydraulic module and variable-speed pump - pressure differential control ............39 13.4  -  Units with hydraulic module and variable-speed pump - temperature difference control ............39 13.5  -  Plate heat exchanger pressure drop (including internal piping) - units without hydraulic module ......... 40 13.6  -  Pump pressure/flow rate curve - units with hydronic module (fixed-speed or variable-speed pump, 50 Hz) ......40 13.7  -  Available external static pressure - units with hydraulic module (fixed-speed or variable-speed pump, 50 Hz) ....41 14 - START-UP ....................................
  • Page 4: Introduction

    1 - INTRODUCTION 1.2 - Check equipment received Prior to the initial start-up of the 30RQS/30RQSY units, the people  involved should be thoroughly familiar with these instructions and  ■ Inspect  the  unit  for  damage  or  missing  parts.  If  damage  is  the specific project data for the installation site. detected, or if shipment is incomplete, immediately file a claim  The 30RQS/30RQSY heat pumps are designed to provide a very  with the shipping company. high  level  of  safety  and  reliability  making  installation,  start-up,  ■ Confirm that the unit received is the one ordered. Compare the  operation  and  maintenance  easier  and  more  secure.  They  will  name plate data with the order.
  • Page 5 1 - INTRODUCTION Over pressure Safety protection in case of accessories an external fire Refrigerant Side High pressure switch External relief valve Rupture disk Fuse plug Heat transfert fluid side External relief valve (1)  Classified for protection in normal service situations. (2)  Classified for protection in abnormal service situations. These accessories are  sized for fires with a thermal flow of 10kW/m². No combustible matter should be  placed within 6.5m of the unit. (3)  The instantaneous over-pressure limited to 10% of the operating pressure does  not apply to this abnormal service situation. The control pressure can be higher  Maxi 10% than  the  service  pressure.  In  this  case  either  the  design  temperature  or  the  high-pressure switch ensures that the service pressure is not exceeded in normal ...
  • Page 6: Equipment And Components Under Pressure

    These  products  incorporate  equipment  or  components  under  If any maintenance operations are carried out on the unit, pressure,  manufactured  by  Carrier  or  other  manufacturers.  We  lock the power supply circuit in the open position and secure recommend  that  you  consult  your  appropriate  national  trade ...
  • Page 7: Repair Safety Considerations

    - Test protocols have serious or even fatal consequences and damage the - Recommissioning of the equipment. installation. Consult Carrier Service for this type of test. Carrier mentions here  Never exceed the specified maximum operating pressures. only the principle of a test without removing the pressure switch: Verify the allowable maximum high- and low-side test - Verify  and  and  record  the  set-points  of  pressure  switches ...
  • Page 8 1 - INTRODUCTION Do not attempt to remove refrigerant circuit components or fittings, while the machine is under pressure or while it is running. Be sure pressure is at 0 kPa and that the unit has been shut-down and de-energised before removing components or opening a circuit.
  • Page 9: Moving And Siting The Unit

    2 - MOVING AND SITING THE UNIT 2.1 - Moving 2.3 - Checks before system start-up See chapter 1.3 - “Installation safety considerations”. Before  the  start-up  of  the  refrigeration  system,  the  complete  installation,  including  the  refrigeration  system  must  be  verified  2.2 - Siting the unit against the installation drawings, dimensional drawings, system ...
  • Page 10: Installation Specifics For 30Rqsy Units

    3 - INSTALLATION SPECIFICS FOR 30RQSY UNITS 3.1 - General Each fan is controlled by a variable-speed controller. Therefore  each  circuit  operates  independently  and  must  have  a  separate  duct  system  to  avoid  any  air  recycling  between  the  air  heat  exchangers of the different refrigerant circuits.  On  the  30RQSY  units  each  fan  includes  a  factory-mounted  connection frame interface for the connection to the duct network ...
  • Page 11: Electrical Protection Of The Fan Motors

    3.6 - Installation of the accessory condensate collection pan Ref.: 30RY 900 032 EE – (30RQSY 039 to 078) Unit with grille protection option It  may  be  necessary  to  remove  water.  Carrier  can  supply  an  NOTE: The discharge lines must be ducted separately. accessory  condensate  collection  pan  for  installation  under  the    Fan motor access hatches (provide a 700 x 700 mm hatch) for each single and  dual duct unit.  The  connection  of  this  pan  to  the  condensate  collection ...
  • Page 12: Dimensions, Clearances

    4 - DIMENSIONS, CLEARANCES 4.1 - 30RQS 039 and 045-078, units with and without hydraulic module For units with fans with variable available pressure (30RQSY) please refer to the pages that follow. Legend NOTES: All dimensions are given in mm. A Non-certified drawings. Control box Refer to the certified dimensional drawings supplied with the unit or available on request, when designing an Water inlet.
  • Page 13: 30Rqs 080-160, Units With And Without Hydraulic Module

    4 - DIMENSIONS, CLEARANCES 4.2 - 30RQS 080-160, units with and without hydraulic module For units with fans with variable available pressure (30RQSY) please refer to the pages that follow. Unit with grille protection option Legend NOTES: All dimensions are given in mm. A Non-certified drawings. Control box Refer to the certified dimensional drawings supplied with the unit or available on request, when designing an Water inlet.
  • Page 14: 30Rqsy 039-045, Units With And Without Hydraulic Module, Without Filter Frame

    4 - DIMENSIONS, CLEARANCES 4.3 - 30RQSY 039-045, units with and without hydraulic module, without filter frame Legend All dimensions are given in mm. Control box Water inlet. Water outlet Required clearances for air flow Recommended clearances for maintenance Air outlet, do not obstruct Power cable entry NOTES: A Non-certified drawings. Refer to the certified dimensional drawings supplied with the unit or available on request, when designing an installation.
  • Page 15: 30Rqsy 039-045, Option 23B, Units With And Without Hydraulic Module, With Filter Frame

    4 - DIMENSIONS, CLEARANCES 4.4 - 30RQSY 039-045, option 23B, units with and without hydraulic module, with filter frame Legend All dimensions are given in mm. Control box Water inlet. Water outlet Required clearances for air flow Recommended clearances for maintenance Air outlet, do not obstruct Power cable entry NOTES: A Non-certified drawings. Refer to the certified dimensional drawings supplied with the unit or available on request, when designing an installation.
  • Page 16: 30Rqsy 050-078, Units With And Without Hydraulic Module, Without Filter Frame

    4 - DIMENSIONS, CLEARANCES 4.5 - 30RQSY 050-078, units with and without hydraulic module, without filter frame Legend All dimensions are given in mm. Control box Water inlet. Water outlet Required clearances for air flow Recommended clearances for maintenance Air outlet, do not obstruct Power cable entry NOTES: A Non-certified drawings. Refer to the certified dimensional drawings supplied with the unit or available on request, when designing an installation.
  • Page 17: 30Rqsy 050-078 Option 23B, Units With And Without Hydraulic Module, With Filter Frame

    4 - DIMENSIONS, CLEARANCES 4.6 - 30RQSY 050-078 option 23B, units with and without hydraulic module, with filter frame Legend All dimensions are given in mm. Control box Water inlet. Water outlet Required clearances for air flow Recommended clearances for maintenance Air outlet, do not obstruct Power cable entry NOTES: A Non-certified drawings. Refer to the certified dimensional drawings supplied with the unit or available on request, when designing an installation.
  • Page 18: 30Rqsy 080-120 Units With And Without Hydraulic Module

    4 - DIMENSIONS, CLEARANCES 4.7 - 30RQSY 080-120 units with and without hydraulic module Legend All dimensions are given in mm. Control box Water inlet. Water outlet Required clearances for air flow Recommended clearances for maintenance Air outlet, do not obstruct Power cable entry NOTES: A Non-certified drawings. Refer to the certified dimensional drawings supplied with the unit or available on request, when designing an installation.
  • Page 19: 30Rqsy 140-160 Units With And Without Hydraulic Module

    4 - DIMENSIONS, CLEARANCES 4.8 - 30RQSY 140-160 units with and without hydraulic module Unit with grille protection option Legend All dimensions are given in mm. Control box Water inlet. Water outlet Required clearances for air flow Recommended clearances for maintenance Air outlet, do not obstruct Power cable entry NOTES: A Non-certified drawings. Refer to the certified dimensional drawings supplied with the unit or available on request, when designing an installation.
  • Page 20: 30Rqs/Rqsy 039-078 Units With Buffer Tank Module

    4 - DIMENSIONS, CLEARANCES 4.9 - 30RQS/RQSY 039-078 units with buffer tank module NOTES: Legend All dimensions are given in mm. A Non-certified drawings. Control box Refer to the certified dimensional drawings supplied with the unit or available on request, when designing an Water inlet. installation. For the location of fixing points, weight Water outlet distribution and coordinates of the centre of gravity refer Required clearances for air flow...
  • Page 21: 30Rqs/Rqsy 080-160 Units With Buffer Tank Module

    4 - DIMENSIONS, CLEARANCES 4.10 - 30RQS/RQSY 080-160 units with buffer tank module NNOTES: Legend All dimensions are given in mm. A Non-certified drawings. Control box Refer to the certified dimensional drawings supplied with the unit or available on request, when designing an Water inlet. installation. For the location of fixing points, weight Water outlet distribution and coordinates of the centre of gravity refer Required clearances for air flow...
  • Page 22: 30Qbs/Rqsy 039-080 Units With Desuperheater

    4 - DIMENSIONS, CLEARANCES 4.11 - 30QBS/RQSY 039-080 units with desuperheater Position of the desuperheater inlets and outlets 4.12 - 30RQS/RQSY 090-120 units with desuperheater Position of the desuperheater inlets and outlets 4.13 - 30RQS/RQSY 140-160 units with desuperheater Position of the desuperheater inlets and outlets Unit with grille protection option   Unit water inlet and outlet   Water inlet and outlet, unit with option 49...
  • Page 23: Physical Data, 30Rqs Units

    5 - PHYSICAL DATA, 30RQS UNITS For units with fans with variable available pressure (30RQSY 039-160) please refer to chapter 7. 30RQS Sound levels Standard unit Sound power level dB(A) Sound pressure level at 10 m dB(A) Standard unit + option 15LS Sound power level  dB(A) Sound pressure level at 10 m  dB(A) Dimensions Lenght 1090 1090 1090 1090 1090 1090 2273 2273 2273 2273 2273 2273 Depth 2109 2109 2109 2109 2109 2109 2136 2136 2136 2136 2136 2136 Height without buffer tank module 1330 1330 1330 1330 1330 1330 1330 1330 1330 1330 1330 1330...
  • Page 24: Electrical Data, 30Rqs Units

    6 - ELECTRICAL DATA, 30RQS UNITS For units with fans with variable available pressure (30RQSY 039-160) please refer to chapter 8. 30RQS - standard unit (without hydraulic module) Power circuit Nominal power supply V-ph-Hz 400-3-50 Voltage range 360-440 Control circuit supply 24 V, via internal transformer Maximum start-up current (Un) Standard unit Unit with electronic starter option Unit power factor at maximum capacity 0.83 0.81 0.81 0.83 0.81 0.78...
  • Page 25: Physical Data, 30Rqsy Units

    7 - PHYSICAL DATA, 30RQSY UNITS 30RQSY Sound levels Standard unit - for 160 Pa external static pressure Sound power level at discharge dB(A) Sound pressure level radiated  dB(A) Sound pressure level at 10 m  dB(A) If two values are shown the first one is for standard units and the second one for units  Dimensions with option 23B 2142/ 2142/ 2142/ 2142/ 2142/ 2142/ Length 2273 2273 2273 2273 2273 2273 2307 2307 2307...
  • Page 26: Electrical Data, 30Rqsy Units

    8 - ELECTRICAL DATA, 30RQSY UNITS 30RQSY - standard unit (without hydraulic module) Power circuit Nominal power supply V-ph-Hz 400-3-50 Voltage range 360-440 Control circuit supply 24 V, via internal transformer Maximum start-up current (Un) Standard unit Unit with electronic starter option Unit power factor at maximum capacity 0.83 0.81 0.81 0.83 0.81 0.83 0.83...
  • Page 27: Electrical Data, 30Rqs And 30Rqsy Units

    2850 2850 2850 2850 2850 2850 2850 2850 2890 2890 2870 2870 Disassembly using standard tools. Disposal and recycling using an  Product disassembly, recycling or disposal at end of life  appropriate company. 12 Operating conditions for which the motor is specifically designed I  - Altitudes above sea level < 1000†† II   - Ambient air temperature °C < 55 Please refer to the operating conditions given in this manual or in the  IV   - Maximum air temperature °C specific conditions in the Carrier selection programs. V   - Potentially explosive atmospheres Non-ATEX environment (1)  Required by regulation 640/2009 with regard to the application of directive 2009/125/EC on the eco-design requirements for electric motors (2)  Item number imposed by regulation 640/2009, annex I2b. (3)  Description given by regulation 640/2009, annex I2b. (4)  To obtain the maximum power input for a unit with hydraulic module add the maximum unit power input from the electrical data table to the pump power input. †  To obtain the maximum unit operating current draw for a unit with hydraulic module add the maximum unit current draw from the electrical data table to the pump current  draw. ††  Above 1000 m, a degradation of 3% for each 500 m should be taken into consideration.
  • Page 28: Compressor Usage And Electrical Data For Standard Units

    12 Operating conditions for which the motor is specifically designed I  - Altitudes above sea level < 1000†† II   - Ambient air temperature °C < 55 Please refer to the operating conditions given in this manual or in the  IV   - Maximum air temperature °C specific conditions in the Carrier selection programs. V   - Potentially explosive atmospheres Non-ATEX environment (1)  Required by regulation 640/2009 with regard to the application of directive 2009/125/EC on the eco-design requirements for electric motors (2)  Item number imposed by regulation 640/2009, annex I2b. (3)  Description given by regulation 640/2009, annex I2b. (4)  To obtain the maximum power input for a unit with hydraulic module add the maximum unit power input from the electrical data table to the pump power input. †  To obtain the maximum unit operating current draw for a unit with hydraulic module add the maximum unit current draw from the electrical data table to the pump current  draw. ††  Above 1000 m, a degradation of 3% for each 500 m should be taken into consideration. 9.3 - Compressor usage and electrical data for standard units...
  • Page 29 Caution: If particular aspects of an actual installation do not conform to the the requirements of the installation directives. Conformance with EN 60204-1 is  conditions described above, or if there are other conditions which should the best means of ensuring compliance with the Machines Directive § 1.5.1.  be considered, always contact your local Carrier representative. • Annex  B  of  EN  60204-1  describes  the  electrical  characteristics  used  for  the  (1)  The absence of main power disconnect switch on standard machines is an exception  operation of the machines.
  • Page 30: Application Data

    °C protection option to -20°C (option 42B) Kit with buffer tank (option 307) and frost  °C protection option to -20°C (option 42B) Note: Do not exceed the maximum operating temperature. (1)  Defines the frost-free temperature of the hydraulic components for use without  Note: Do not exceed the maximum operating temperature. glycol. (1)  For entering water temperatures below 7.5°C at start-up, contact Carrier. (2)  For low-temperature applications, where the leaving water temperature is below  30RQS/RQSY - heating mode 5°C, a frost protection solution must be used. (3)  For  transport  and  storage  of  the  30RQS/30RQSY  units  the  minimum  and  maximum allowable temperatures are -20°C and +48°C. It is recommended that  these temperatures are used for transport by container. (4)  Defines the frost-free temperature of the hydraulic components for use without  glycol. 30RQS/RQSY - cooling mode Entering air temperature, °C...
  • Page 31: Minimum Water Flow Rate

    10 - APPLICATION DATA 10.4 - Minimum water flow rate 10.6.2 - Maximum water loop volume Units with hydraulic module incorporate an expansion tank that  If the installation flow rate is below the minimum flow rate, there  limits the water loop volume. The table below gives the maximum  is a risk of excessive fouling. loop  volume  for  pure  water  or  ethylene  glycol  with  various  10.5 - Maximum water heat exchanger water concentrations. flow rate 039-078 without 080-160 without 30RQS/RQSY...
  • Page 32: Electrical Connection

    The power supply must conform to the specification on the heat  the characteristics and regulations applicable to each installation  pump nameplate. The supply voltage must be within the range  site. The following is only to be used as a guide-line, and does not  specified in the electrical data table. For connec-tions refer to the  make  Carrier  in  any  way  liable.  After  wire  sizing  has  been  wiring diagrams and the certified dimen-sional drawings. completed, using the certified dimen-sional drawing, the installer  WARNING: Operation of the heat pump with an improper must  ensure  easy  connection  and  define  any  modifications  supply voltage or excessive phase imbalance constitutes necessary on site.
  • Page 33: Field Control Wiring

    11 - ELECTRICAL CONNECTION 11.5 - Field control wiring IMPORTANT: Field connection of interface circuits may lead to safety risks: any control box modification must maintain equipment conformity with local regulations. Precautions must be taken to prevent accidental electrical contact between circuits supplied by different sources: •...
  • Page 34: Water Connections

    It must be located in a position that is easily accessible for removal and cleaning. Carrier recommendations on heat exchange fluids: The mesh size of the filter must be 1.2 mm. • No  NH  ...
  • Page 35: Protection Against Cavitation (Option 116)

    If the heat transfer fluid does not comply with the Carrier regu- lations, the nitrogen charge must be added immediately. 12.4 - Protection against cavitation (option 116) To ensure the durability of the pumps in the integrated hydraulic ...
  • Page 36 12 - WATER CONNECTIONS Typical hydraulic circuit diagram with hydraulic module Option Option Option Typical hydraulic circuit diagram without hydraulic module Legend Components of the unit and hydraulic module Installation components 1  Screen filter (Mesh1.2 mm) 16  Thermowell 2  Expansion tank (option) 17  Air purge  3  Discharge valve 18 ...
  • Page 37 12 - WATER CONNECTIONS Hydraulic module - sizes 039-078 Hydraulic module - sizes 080-160 Dual pump shown Dual pump shown Hydraulic module - sizes 039-080 Hydraulic module - sizes 090-160 Dual pump and buffer tank shown Dual pump and buffer tank shown...
  • Page 38: Nominal System Water Flow Control

    13 - NOMINAL SYSTEM WATER FLOW CONTROL 13.1.3 - Procedure for controlling the water flow Refer to the chapter ‘‘Water connections’’ for all references points mentioned in this chapter. Once the circuit is cleaned, read the pressures on the pressure  The water circulation pumps of unit range have been designed to  gauges (water inlet and outlet pressure) determine the pressure  allow the hydraulic modules to operate at each possible conditions,  drop within the unit (plate heat exchanger + internal pipe work). i.e. with chilled water temperature differences at full load from 3  Compare the value obtained with the design value predicted by  to 10 K. the selection software. This temperature difference required between the water inlet and  If  the  pressure  drop  reading  is  above  the  specified  value,  this  outlet ...
  • Page 39: Units With Hydraulic Module And Variable-Speed Pump - Pressure Differential Control

    The  temperature  probes  at  the  heat  exchanger  inlet  and  outlet  flow rate or maximum frequency and this results in a lower  (items 8 and 9 in the typical hydraulic circuit diagram) are used  pressure differential than the set point. as means of control. • If the set point value is too low (achieved for a lower flow  The system reads the measured temperature values, calculates  rate that the minimum value or a lower frequency than the  the corresponding temperature difference, compares it with the  minimum  value),  the  system  settles  at  the  minimum  flow  user-selected set point value and modulates the pump speed as  rate  or  minimum  frequency  and  this  results  in  a  higher  necessary: pressure differential than the set point. • If a higher delta T value than the set point is measured, the  See with Carrier Service to implement the procedures described  flow rate is increased. below. • If a lower delta T value than the set point is measured, the  flow rate is decreased.
  • Page 40: Plate Heat Exchanger Pressure Drop (Including Internal Piping) - Units Without Hydraulic Module

    Modify the control parameters: • If the set point value is too low (achieved for a higher flow  - Set water flow control to ‘temperature differential’ rate that the maximum value or a higher frequency than the  - Set the value of the required differential temperature. maximum value), the system settles at the maximum flow  By default, the unit is factory configured at the minimum speed  rate or maximum frequency and this results in a higher delta  (frequency: 50 Hz). T value than the set point. See with Carrier Service to implement the procedures described  below. 13.5 - Plate heat exchanger pressure drop (including internal piping) - units without hydraulic module 30RQS/RQSY 039-078 30RQS/RQSY 080-160 Water flow rate, l/s Water flow rate, l/s Legend Legend 30RQS/30RQSY 039 30RQS/30RQSY 060 30RQS/30RQSY 080 ...
  • Page 41: Available External Static Pressure - Units With Hydraulic Module (Fixed-Speed Or Variable-Speed Pump, 50 Hz)

    13 - NOMINAL SYSTEM WATER FLOW CONTROL 13.7 - Available external static pressure - units with hydraulic module (fixed-speed or variable- speed pump, 50 Hz) Data applicable for: - Fresh water 20 °C - In case of use of the glycol, the maximum water flow is reduced. Warning : With the buffer tank module option, the curves below do not take the pressure drops for this component into account.
  • Page 42: Start-Up

    14 - START-UP 14.1 - Preliminary checks Standard configuration: return water control Never be tempted to start the heat pump without reading fully, and  understanding,  the  operating  instructions  and  without  having  carried out the following pre-start checks: • Check the chilled water circulation pumps, air handling units  and all other equipment connected to the evaporator.  • Refer to the manufacturer’s instructions. • For units without hydraulic module, the water pump overheat  protection device must be connected in series with the pump  contactor power supply.  • Refer to the wiring diagram supplied with the unit. • Ensure that there are no refrigerant leaks. • Confirm that all pipe securing bands are tight. • Confirm that the electrical connections are secure. 14.2 - Actual start-up IMPORTANT: •...
  • Page 43: Supplementary Electric Resistance Heaters

    14 - START-UP 14.4 - Supplementary electric resistance Typical accessory installation diagram heaters To permit staging of the capacity reduction of the heat pump at  low ambient temperatures, as shown in the diagram below, it is  possible to install supplementary electric heaters in the leaving  water line. Their capacity can compensate for the capacity drop  of the heat pump. These heaters can be controlled via an electronic card mounted  on a board (option).  Four outputs are available to control the heater contactors (not  supplied with the board), permitting gradual compensation of the  heat pump capacity reduction. These outputs are configurable to obtain a choice of two, three or  four stages. The last stage will only be activated after a shut-down  of the heat pump following a fault con-dition (safety device). In the diagram below “example of additional electric heaters” the  capacity of the four heaters is the same as the capacity of the heat  pump at 7°C outdoor air temperature. This requires only a 400 V-3 ph-50 Hz power supply source, as  well as a connection to the unit via a communication bus. For the required configuration of the stages consult the 30RB/RQ  Touch Pilot Junior Control IOM. Legend 1  Electric heater power supply 400 V-3 ph-50 Hz 2  Accessory control board for four additional electric heaters 3  Internal communication bus 4 ...
  • Page 44: Major System Components

    15 - MAJOR SYSTEM COMPONENTS 15.1 - Compressors 15.4 - Fans 30RQS/RQSY  units  use  hermetic  scroll  compressors.  Each  The fans are axial Flying Bird fans equipped with rotating shroud  compressor is equipped with a crankcase oil heater, as standard. and made of composite recyclable material. The motors are three- phase, with permanently lubricated bearings and insulation class  Each compressor sub-function is equipped with: F. See table below. • Anti-vibration mountings between the unit chassis and the  chassis of the compressor sub-function. 15.5 - Electronic expansion valve (EXV) • A single pressure safety switch at the discharge. The EXV is equipped with a stepper motor that is controlled via  15.2 - Lubricant the SIOB board. The compressors installed in these units have a specific oil charge, ...
  • Page 45: Water Evaporator/Condenser

    For  the  alarm  containers during the water piping connection procedure must be  acknowledgements refer to the 30RB/RQ Touch Pilot Junior control  chemically neutral in relation to the materials and coatings to which  manual). they are applied. This is also the case for the products originally  supplied by Carrier SCS. 15.11 - Storage tank NOTES - Monitoring during operation: 30RQS/RQSY  units  are  equipped  with  mechanically  welded  • Follow the regulations on monitoring pressurised storage tanks that permit storing the excess charge when the unit  equipment.
  • Page 46: Options

    16 - OPTIONS Options Description Advantages Improved corrosion resistance,  Corrosion protection,  Fins made of pre-treated aluminium  30RQS/RQSY recommended for moderate marine and  traditional coils (polyurethane and epoxy) 039-160 urban environments Low temperature chilled water production  Medium-temperature brine  Covers specific applications such as ice  30RQS/RQSY down to 0°C with ethylene glycol and  solution storage and industrial processes 039-160 propylene glycol.  Low temperature chilled water production  Low-temperature brine  Covers specific applications such as ice  30RQS/RQSY down to -15°C with ethylene glycol and -12°C  solution storage and industrial processes 039-160 with propylene glycol.  Acoustic compressor enclosure and low-speed  Noise emission reduction at reduces fan  Very low noise level 15LS 30RQS 039-160 fans  speed Very low noise level 15LS Acoustic compressor enclosure Compressor noise emission reduction...
  • Page 47 16 - OPTIONS Options Description Advantages Dual high-pressure water pump with variable  speed drive (VSD), water filter, electronic flow  Easy and fast installation (plug & play),  switch, pressure transducers. Multiple  HP variable-speed dual- significant pumping energy cost savings  30RQS/RQSY 116W possibilities of water flow control.  For more  pump hydraulic mod. (more than two-thirds), tighter water flow  039-160 details, refer to the dedicated chapter  control, improved sytem reliability (expansion tank not included Option with  built-in safety hydraulic components available) Two-directional communication board  Connects the unit by communication bus to  30RQS/RQSY J-Bus gateway 148B complying with JBus protocol a building management system  039-160 Two-directional communication board  Connects the unit by communication bus to  30RQS/RQSY Lon gateway 148D complying with Lon Talk protocol a building management system  039-160 Easy and high-speed connection by  Two-directional high-speed communication  ethernet line to a building management ...
  • Page 48: Specific Details For Units With A Fan With Available Static Pressure (30Rqsy)

    17 - SPECIFIC DETAILS FOR UNITS WITH A FAN WITH AVAILABLE STATIC PRESSURE (30RQSY) Selection based on the pressure drop The cooling and heating capacities are given for an available pressure of 160 Pa and for a unit without filter. To calculate the performances at other pressure drops please use the correction factors below. ■ Cooling mode 30RQSY 039-050/30RQSY 080-120 Duct pressure drop Fan speed, r/s Power input coefficient Cooling capacity coefficient 12.00 0.943 1.019...
  • Page 49: Partial Heat Reclaim Using Desuper-Heaters (Option 49)

    18 - PARTIAL HEAT RECLAIM USING DESUPER-HEATERS (OPTION 49) This option permits the production of free hot water using heat reclaim by desuperheating the compressor discharge gases. The option  is available for the whole 30RQS/30RQSY range. A plate heat exchanger is installed in series with the air condenser coils on the compressor discharge line of each circuit. The control configuration for the desuperheater option is factory assembled. 18.1 - Physical data, 30RQS/30RQSY units with partial heat reclaim using desuperheaters (option 49) 30RQS/RQSY partial heat reclaim mode Operating weight 30RQS units with RTPF coils Standard unit without hydraulic module 1073 1091 Standard unit with hydraulic module option Single high-pressure pump...
  • Page 50: Installation And Operation Of The Heat Reclaim With Desuperheater Option

    18 - PARTIAL HEAT RECLAIM USING DESUPER-HEATERS (OPTION 49) 18.2 - Installation and operation of the heat During the unit installation the heat reclaim plate heat exchangers  reclaim with desuperheater option must be insulated and frost protected, if required. Please refer to the typical installation diagram below for the main  The  30RQS/RQBSY  units  with  the  desuperheater  option  are  components  and  functions  of  the  30RQS/RQSY  units  with  the  supplied with one heat exchanger per refrigerant circuit.
  • Page 51: Installation

    18 - PARTIAL HEAT RECLAIM USING DESUPER-HEATERS (OPTION 49) 18.3 - Installation 18.5 - Operating limits The  water  connections  on  the  desuperheater  water  inlets  and  Desuperheater Minimum Maximum outlets must not cause any mechanical local constraint at the heat  exchangers. If necessary, install flexible connection sleeves. Entering water temperature at start-up °C Install  water  flow  control  and  balancing  valves  at  the  heat  Leaving water temperature during operation °C exchanger outlet.
  • Page 52: Brine Option (Option 5B & Option 6B)

    The presence of glycol reduces the life of the pump fittings. It is recommended that the commissioning of a brine system is  It is recommended to change the fittings or the pump: done by Carrier. • every 40 000 hours for applications with water, For information: The protection values given by our supplier, based  • every 15 000 hours for applications with glycol on the antifreeze solutions used in the Carrier Montluel laboratory, ...
  • Page 53: Standard Maintenance

    NOTE: Any deviation or non-observation of these maintenance criteria will render the guarantee conditions for the HVAC unit Mechanical checks nul and void, and the manufacturer, Carrier SCS, will no longer be held responsible. • Check the tightening of the fan tower, fan, compressor and  control box fixing bolts.
  • Page 54: Tightening Torques For The Main Electrical Connections

    20 - STANDARD MAINTENANCE 20.4 - Tightening torques for the main electrical 20.6 - Air heat exchanger connections We recommend, that finned coils are inspected regularly to check  the degree of fouling. This depends on the environment where the  Designation Value Component/screw type unit  is  installed,  and  will  be  worse  in  urban  and  industrial  in the unit (N·m) installations and near trees that shed their leaves. Soldered screw (PE) customer connection For coil cleaning, two maintenance levels are used, based on the ...
  • Page 55: Characteristics Of R-410A

    20 - STANDARD MAINTENANCE 20.9 - Characteristics of R-410A Saturated temperatures (°C) based on the relative pressure (in kPa) Relative Relative Relative Relative Saturat. temp. Saturat. temp. Saturat. temp. Saturat. temp. pressure pressure pressure pressure 1687 3088 1734 3161 1781 3234 1830 3310...
  • Page 56: Start-Up Checklist For 30Rqs/30Rqsy Heat Pumps (Use For Job File)

    21 - START-UP CHECKLIST FOR 30RQS/30RQSY HEAT PUMPS (USE FOR JOB FILE) Preliminary information Job name: ........................................ Location: ........................................Installing contractor: ....................................Distributor: ....................................... Start-up performed by:..............  Date:  ................... Equipment Model 30RQS/RQSY: ..............S/N ....................Compressors Circuit A Circuit B 1.  Model No.  ................  1.    M odel No.................  ...
  • Page 57 21 - START-UP CHECKLIST FOR 30RQS/30RQSY HEAT PUMPS (USE FOR JOB FILE) Check water heat exchanger water loop Water loop volume   = ....   (litres) Calculated volume  = ....   (litres) 3.25 litres/nominal kW capacity for air conditioning 6.5 litres/nominal kW capacity for process cooling  Proper loop volume established  Proper loop corrosion inhibitor included ....litres of ...... Proper loop freeze protection included (if required) ......litres of ...... Water piping includes electric tape heater up to the water heat exchanger  Return water piping is equipped with a screen filter with a mesh size of 1.2 mm Check pressure drop across water heat exchanger (no hydraulic module) or the external static pressure (with hydraulic module) Entering water heat exchanger = ...
  • Page 58 CARRIER participates in the ECP programme for LCP/HP Check ongoing validity of certificate: www.eurovent-certification.com Order No.: 13465, 09.2018. Supersedes order No.: 13465, 01.2017. Manufactured by: Carrier SCS, Montluel, France. Manufacturer reserves the right to change any product specifications without notice.

Table of Contents