13 - NOMINAL SYSTEM WATER FLOW CONTROL
This flow rate variation is realised, observing the minimum and 
maximum admissible unit flow rates as well as the minimum and 
maximum pump supply frequency values.
The  delta  T  value  maintained  can  in  certain  cases  be  different 
from the set point value:
• If the set point value is too high (achieved for a lower flow 
rate than the minimum value or a lower frequency than the 
minimum  value),  the  system  settles  at  the  minimum  flow 
rate or minimum frequency and this results in a lower delta 
T value than the set point.
• If the set point value is too low (achieved for a higher flow 
rate that the maximum value or a higher frequency than the 
maximum value), the system settles at the maximum flow 
rate or maximum frequency and this results in a higher delta 
T value than the set point.
See with Carrier Service to implement the procedures described 
below.

13.5 - Plate heat exchanger pressure drop (including internal piping) - units without hydraulic module

30RQS/RQSY 039-078
150
140
130
120
110
100
90
80
70
60
50
40
30
20
10
0
0,0
0,5
1,0
1,5
2,0
Water flow rate, l/s
Legend
1.
30RQS/30RQSY 039
2.
30RQS/30RQSY 045
3.
30RQS/30RQSY 050
13.6 - Pump pressure/flow rate curve - units with hydronic module (fixed-speed or variable-speed
pump, 50 Hz)
Low-pressure pumps
250
230
210
190
170
150
130
110
90
70
50
0
1
2
3
4
Water flow rate, l/s
Legend
1.
30RQS/30RQSY 039-090 
2.
30RQS/30RQSY 100-120
3.
30RQS/30RQSY 140-160
40
5
4
2
3
6
1
2,5
3,0
3,5
4,0
4,5
5,0
4.
30RQS/30RQSY 060
5.
30RQS/30RQSY 070
6.
30RQS/30RQSY 078
1
2
3
5
6
7
8
9
10
13.4.1 - Procedure for cleaning the hydraulic circuit
Refer  to  the  procedure  for  cleaning  the  hydraulic  circuit  from 
chapter 13.3.1
13.4.2 - Procedure for controlling the Delta T° setpoint
Once the circuit is cleaned, stop the forced start of the pump and 
proceed  to  the  configuration  of  the  unit  for  the  required  control 
mode.
Modify the control parameters:
- Set water flow control to 'temperature differential'
- Set the value of the required differential temperature.
By default, the unit is factory configured at the minimum speed 
(frequency: 50 Hz).
180
170
160
150
140
130
120
110
100
90
80
70
60
50
40
30
20
10
0
0
1
2
5,5
6,0
Legend
1.
30RQS/30RQSY 080 
2.
30RQS/30RQSY 090
3.
30RQS/30RQSY 100
250
230
210
190
170
150
130
110
90
70
50
11
12
0
1
2
Legend
1.
30RQS/30RQSY 039-100 
2.
30RQS/30RQSY 120-160
30RQS/RQSY 080-160
3
2
1
3
4
5
6
7
8
Water flow rate, l/s
4.
30RQS/30RQSY 120
5.
30RQS/30RQSY 140
6.
30RQS/30RQSY 160
High-pressure pumps
1
3
4
5
6
7
8
Water flow rate, l/s
6
5
4
9
10
11
12
2
9
10
11
12