Carrier AQUAZONE 50RHC Installation And Service Instructions Manual

Water source heat pump units
Hide thumbs Also See for AQUAZONE 50RHC:
Table of Contents

Advertisement

CONTENTS
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . .1,2
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-26
Step 1 - Check Jobsite . . . . . . . . . . . . . . . . . . . . . . . . 2
Step 2 - Check Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
• STORAGE
• PROTECTION
Step 3 - Unit Location. . . . . . . . . . . . . . . . . . . . . . . . . . 14
• FIELD CONVERSION OF DISCHARGE AIR
Step 4 - Mounting the Unit . . . . . . . . . . . . . . . . . . . . . 15
Step 5 - Duct System . . . . . . . . . . . . . . . . . . . . . . . . . . 15
• SOUND ATTENUATION
• EXISTING DUCT SYSTEM
Step 6 - Condensate Drain . . . . . . . . . . . . . . . . . . . . . 16
• VENTING
Step 7 - Piping Connections . . . . . . . . . . . . . . . . . . . 16
Step 8 - Field Power Supply Wiring . . . . . . . . . . . . 18
• POWER CONNECTION
• 208-VOLT OPERATION
Step 9 - Field Control Wiring . . . . . . . . . . . . . . . . . . . 18
• WATER SOLENOID VALVES
PRE-START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26-30
System Checkout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
PSC Blower Speed Selection . . . . . . . . . . . . . . . . . . 27
FIELD SELECTABLE INPUTS . . . . . . . . . . . . . . . 30-32
C Control Jumper Settings . . . . . . . . . . . . . . . . . . . . 30
C Control DIP Switches . . . . . . . . . . . . . . . . . . . . . . . 30
D Control Jumper Settings . . . . . . . . . . . . . . . . . . . . 30
D Control DIP Switches . . . . . . . . . . . . . . . . . . . . . . . 30
(HWR) Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Water Valve (Slow Opening) . . . . . . . . . . . . . . . . . . . 32
Outside Air Damper (OAD) . . . . . . . . . . . . . . . . . . . . 32
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32-36
Operating Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Scroll Compressor Rotation. . . . . . . . . . . . . . . . . . . . . 33
Unit Start-Up Cooling Mode . . . . . . . . . . . . . . . . . . . . . 33
Unit Start-Up Heating Mode . . . . . . . . . . . . . . . . . . . . . 34
Flow Regulation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53500007-01
Book 1
4
Tab
5a 5a
Installation, Start-Up, and
Service Instructions
Page
Printed in U.S.A.
50RHC,RVC,RHR,RHS,
RVR,RVS,RDS006-060

Water Source Heat Pump Units

Flushing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Antifreeze . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Cooling Tower/Boiler Systems . . . . . . . . . . . . . . . . . . 36
Heat Exchanger Well Systems . . . . . . . . . . . . . . . . 36
OPERATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36,37
Power Up Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Units with HWR Option. . . . . . . . . . . . . . . . . . . . . . . . . . 37
SYSTEM TEST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .37,38
Test Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Retry Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38-40
Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Water Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Condensate Drain Pans . . . . . . . . . . . . . . . . . . . . . . . . . 38
Refrigerant System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Compressor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Fan Motors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Condensate Drain Cleaning . . . . . . . . . . . . . . . . . . . 39
Air Coil Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Condenser Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Checking System Charge . . . . . . . . . . . . . . . . . . . . . 39
Refrigerant Charging . . . . . . . . . . . . . . . . . . . . . . . . . 40
Air Coil Fan Motor Removal . . . . . . . . . . . . . . . . . . . . . 40
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . 40-42
Thermistor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Control Sensors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
IMPORTANT: Read the entire instruction manual before
starting installation.

SAFETY CONSIDERATIONS

Installation and servicing of air-conditioning equipment can
be hazardous due to system pressure and electrical compo-
nents. Only trained and qualified service personnel should
install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance func-
tions of cleaning coils and filters and replacing filters. All other
operations should be performed by trained service personnel.
When working on air-conditioning equipment, observe precau-
tions in the literature, tags and labels attached to the unit, and
other safety precautions that may apply.
Improper installation, adjustment, alteration, service, mainte-
nance, or use can cause explosion, fire, electrical shock or other
conditions which may cause personal injury or property dam-
age. Consult a qualified installer, service agency, or your distrib-
utor or branch for information or assistance. The qualified in-
staller or agency must use factory-authorized kits or accessories
when modifying this product. Refer to the individual instruc-
tions packaged with the kits or accessories when installing.
Form 50R-5SI
Pg 1
AQUAZONE™
Page
6-07
Replaces: 50R-4SI

Advertisement

Table of Contents
loading

Summary of Contents for Carrier AQUAZONE 50RHC

  • Page 1: Table Of Contents

    RVR,RVS,RDS006-060 Water Source Heat Pump Units Flushing ........34 Page Antifreeze .
  • Page 2: General

    • RDS premium efficiency with vertical airflow and bot- tom discharge (downflow) IMPORTANT: The installation of water source heat pump units and all associated components, parts, and accessories which make up the installation shall be in accordance with the regulations of ALL authorities having jurisdiction and MUST conform to all applicable codes.
  • Page 3: Inspect Unit

    STORAGE — If the equipment is not needed immediately at the jobsite, it should be left in its shipping carton and stored in a clean, dry area of the building or in a warehouse. Units must be stored in an upright position at all times. If carton stacking is necessary, stack units a maximum of 3 high.
  • Page 4 Table 1 — Physical Data — Aquazone™ 50RHC,RVC006-060 Units UNIT 50RHC,RVC COMPRESSOR (1 each) FACTORY REFRIGERANT CHARGE R-22 VERTICAL (oz) FACTORY REFRIGERANT CHARGE R-22 HORIZONTAL (oz) PSC FAN MOTOR AND BLOWER Fan Motor Type/Speeds Fan Motor Std/High Static (Hp) Blower Wheel Size (D x W) (in.) Std/High Static WATER CONNECTION SIZE (FPT) VERTICAL Air Coil...
  • Page 5 Table 2 — Physical Data — Aquazone™ 50RHR,RVR006-060 Units UNIT 50RHR,RVR COMPRESSOR (1 each) FACTORY CHARGE R-22 (oz) PSC FAN MOTOR AND BLOWER Fan Motor Type/Speeds Fan Motor (Hp) Blower Wheel Size (D x W) (in.) WATER CONNECTION SIZE (FPT) VERTICAL Air Coil Dimensions (H x W) (in.)
  • Page 6 WATER CONNECTIONS OVERALL CABINET 1 — In 50RHC UNITS Width Depth Height 19.1 34.1 11.0 006-012 48.5 86.6 27.9 24.4 20.1 43.1 17.1 15.3 018-030 51.1 109.5 43.4 38.9 20.1 47.1 21.1 18.8 036-042 51.1 119.6 53.6 47.6 24.1 54.1 21.1 19.4 61.2...
  • Page 7 WATER CONNECTIONS OVERALL CABINET 50RHR UNITS Width Depth Height ensate 006-012 in. 22.4 43.1 11.3 56.8 109.5 28.7 6.1 13.7 015-024 in. 22.4 43.1 17.3 56.8 109.5 43.9 6.1 12.4 22.4 53.2 19.3 56.8 135.1 49.0 6.1 13.7 22.4 53.2 19.3 56.8 135.1...
  • Page 8 WATER CONNECTIONS OVERALL CABINET 50RHS UNITS Cond- Width Depth Height ensate 22.4 53.2 19.3 015-018 56.8 135.1 49.0 13.7 024-030 in. 22.4 62.2 19.3 56.8 158.0 49.0 13.7 22.4 62.2 19.3 56.8 158.0 49.0 13.7 042-048 in. 25.4 71.2 21.3 64.5 180.8 54.1...
  • Page 9 UNIT HANGER ISOLATION DETAIL Fig. 4 — Typical Installation — 50RHC,RHR,RHS Units...
  • Page 10 WATER CONNECTIONS OVERALL CABINET 50RVC UNITS Width Depth Height 19.1 19.1 22.0 9.4 2.8 009-012 48.5 48.5 55.9 7.1 24.0 7.1 21.5 21.5 39.0 3.8 15.2 3.6 018-030 54.6 54.6 99.1 9.7 38.6 9.1 036 & 042 in. 21.5 26.0 44.0 3.7 16.2 2.6 54.6...
  • Page 11 WATER CONNECTIONS OVERALL CABINET 50RVR UNITS Width Depth Height 22.4 21.6 22.6 009-012 56.8 54.9 57.4 22.4 21.6 34.6 015-024 56.8 54.9 87.9 22.4 25.6 40.6 56.8 65.1 103.1 22.4 25.6 40.6 56.8 65.1 103.1 22.4 25.6 48.6 042-048 56.8 65.1 123.4 25.4...
  • Page 12 WATER CONNECTIONS OVERALL CABINET 50RVS UNITS Width Depth Height 22.4 25.6 40.6 015-018 56.8 65.1 103.1 13.7 22.4 25.6 44.6 024-030 56.8 65.1 113.3 13.7 22.4 25.6 48.6 56.8 65.1 123.4 13.7 25.4 30.6 50.6 042-048 64.5 77.8 128.5 13.7 25.4 30.6 54.6...
  • Page 13 WATER CONNECTIONS (in.) OVERALL CABINET 50RDS UNITS Width Depth Height 22.4 25.6 44.6 16.9 13.9 015-018 56.8 65.1 113.3 42.9 35.3 13.7 22.4 25.6 48.6 16.9 13.9 024-030 56.8 65.1 123.4 42.9 35.3 13.7 22.4 25.6 52.6 16.9 13.9 56.8 65.1 133.6 42.9 35.3...
  • Page 14: Step 3 - Unit Location

    Supply Air Building Loop Flexible Connection Water Return Water Field-supplied stainless steel braid hose with integral “ J” swivel Power Thermostat Wiring Ball Valve with optional integral P/T plug Compressor (typical for supply and Access Panel return piping) NOTE: Ball valve with integral pressure temperature plug recommended. Fig.
  • Page 15: Step 4 - Mounting The Unit

    Return Air Supply Duct Side Discharge Return Air Drain Back Discharge Discharge Air Fig. 12 — Conversion Right Return, Side Discharge to Back Discharge Step 4 — Mounting the Unit HORIZONTAL UNITS (50RHC,RHR,RHS) — Horizontal units should be mounted using the factory-installed hangers. Proper attachment of hanging rods to building structure is critical for safety.
  • Page 16: Step 6 - Condensate Drain

    3 types of WSHP piping systems to choose from: water loop, ground-water and ground loop. Refer to Piping Section of Carrier System Design Manual for addi- tional information. All WSHP units use low temperature soldered female pipe...
  • Page 17: Ground-Loop Applications

    Water Supply and Quantity — Check water supply. Water supply should be plentiful and of good quality. See Table 4 for water quality guidelines. IMPORTANT: Failure to comply with the above required water quality and quantity limitations and the closed- system application design requirements may cause damage to the tube-in-tube heat exchanger that is not the responsi- bility of the manufacturer.
  • Page 18: Step 8 - Field Power Supply Wiring

    Step 8 — Field Power Supply Wiring To avoid possible injury or death due to electrical shock, open the power supply disconnect switch and secure it in an open position during installation. Use only copper conductors for field-installed electrical wiring. Unit terminals are not designed to accept other types of conductors.
  • Page 19 — Alarm Relay Contacts — Blower Motor — Blower Motor Capacitor — Blower Relay — Circuit Breaker — Compressor Contactor — Sensor, Condensate Overflow COMPR — Compressor — Sensor, Water Coil Freeze Protection — Sensor, Air Coil Freeze Protection — High-Pressure Switch HWTS —...
  • Page 20 — Alarm Relay Contacts — Blower Motor — Blower Motor Capacitor — Blower Relay — Circuit Breaker — Compressor Contactor — Sensor, Condensate Overflow COMPR — Compressor — Sensor, Water Coil Freeze Protection — Sensor, Air Coil Freeze Protection — High-Pressure Switch —...
  • Page 21 — Alarm Relay Contacts — Blower Motor — Blower Motor Capacitor — Blower Relay — Circuit Breaker — Compressor Contactor — Sensor, Condensate Overflow COMPR — Compressor — Sensor, Water Coil Freeze Protection — Sensor, Air Coil Freeze Protection — High-Pressure Switch HPWS —...
  • Page 22 — Alarm Relay Contacts — Blower Motor — Blower Motor Capacitor — Blower Relay — Circuit Breaker — Compressor Contactor — Sensor, Condensate Overflow COMPR — Compressor — Sensor, Water Coil Freeze Protection — Sensor, Air Coil Freeze Protection — High-Pressure Switch HPWS —...
  • Page 23 a50-8162 Fig. 23 — 50RHC,RVC,RHR,RVR,RHS,RVS,RDS Typical Single-Phase a50-6267tf.tif NOTE: Low voltage connector may be removed for easy installation. Fig. 24 — Low Voltage Field Wiring Line Voltage Power Connection a50-6268tf.tif AQUAZONE CONTROL (C Control Shown) Fig. 25 — Typical Aquazone Control Board TERMINAL STRIP P2 Fig.
  • Page 24 50RHC,RVC VOLTS-PHASE UNITS 60 Hz 208/230-1 006* 265-1 208/230-1 265-1 208/230-1 265-1 208/230-1 265-1 208/230-1 265-1 208/230-3 460-3 208/230-1 265-1 208/230-3 460-3 208/230-1 265-1 208/230-3 460-3 208/230-1 208/230-3 041† 460-3 575-3 208/230-1 208/230-3 460-3 575-3 208/230-1 208/230-3 460-3 575-3 208/230-1 208/230-3 460-3 575-3...
  • Page 25 50RHR,RVR VOLTS-PHASE UNITS 60 Hz 208/230-1 006* 265-1 208/230-1 265-1 208/230-1 265-1 208/230-1 265-1 208/230-1 265-1 208/230-1 265-1 208/230-3 460-3 208/230-1 265-1 208/230-3 460-3 208/230-1 265-1 208/230-3 460-3 208/230-1 208/230-3 460-3 575-3 208/230-1 208/230-3 460-3 575-3 208/230-1 208/230-3 460-3 575-3 LEGEND —...
  • Page 26: Pre-Start-Up

    COMPRESSOR 50RDS, VOLTS- RHS, VOLTAGE PHASE MIN/MAX 60 Hz UNIT 208/230-1 197/254 265-1 239/292 208/230-1 197/254 265-1 239/292 208/230-1 197/254 10.3 265-1 239/292 208/230-3 197/254 460-3 414/506 208/230-1 197/254 12.2 265-1 239/292 10.9 208/230-3 197/254 460-3 414/506 208/230-1 197/254 12.2 265-1 239/292 10.9...
  • Page 27: Psc Blower Speed Selection

    AIR COIL — To obtain maximum performance, clean the air coil before starting the unit. A ten percent solution of dish- washer detergent and water is recommended for both sides of the coil. Rinse thoroughly with water. PSC (Permanent Split Capacitor) Blower All water source heat pumps are Speed Selection —...
  • Page 28 50RHC,RVC RATED UNITS SPEED 0.00 0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40 0.45 0.50 0.60 0.70 0.80 0.90 006* High Static 1010 1000 High Static 1000 1250 1230 1200 1180 1150 1120 1090 1070 1040 1010 1120 1100 1070 1050 1030 1010 1000 High Static 1050 1040 1030 1010 990...
  • Page 29 Table 11 — 50RVC Blower Performance with Wet Coil Table 12 — 50RHS,RVS,RDS Blower Performance 50RHS,RVS,RDS RATED UNITS AIRFLOW SPEED 1000 HS Hi Hi Static 1000 HS Med 1260 1240 1220 1190 1170 1130 1100 1070 1040 HS Low 1170 1150 1130 1100 1080 1050 1020 1150 HS Hi Hi Static...
  • Page 30: Field Selectable Inputs

    2, W1 is used for heating stage 1 and O/W2 is used for heating stage 2. Select ON for heat pump applications. In heat pump mode, Y1 used is for compressor stage 1, Y2 is used for compressor stage 2, W1 is used for heating stage 3 or emergency heat, and O/W2 is used for RV (heating or cooling) depending upon switch 4 setting.
  • Page 31: Units With Modulating Hot Water Reheat

    In the heating mode, the reversing valve is deenergized. Almost any thermostat will activate the heat pump in heating or cooling modes. The Deluxe D microprocessor board, which is standard with the HWR option, will accept either heat pump (Y,O) thermostats or non-heat pump (Y,W) thermostats.
  • Page 32: D Control Accessory Relay Configurations

    Internal Pump (From Water Loop) a50-8145.eps NOTE: All components shown are internal to the heat pump unit. NLL staged heating mode will then provide heating during the NSB period. Water Valve (Slow Opening) — ured for Water Valve (slow opening), the relay will start 60 sec- onds prior to starting compressor relay.
  • Page 33: Operating Limits

    3. Balance airflow at registers. 4. Adjust all valves to the full open position and turn on the line power to all heat pump units. 5. Operate unit in the cooling cycle. Refer to Tables 18 and 19 for unit operating limits.
  • Page 34: Unit Start-Up Heating Mode

    Unit Start-Up Heating Mode NOTE: Operate the unit in heating cycle after checking the cooling cycle. Allow 5 minutes between tests for the pressure or reversing valve to equalize. 1. Turn thermostat to lowest setting and set thermostat switch to HEAT position. 2.
  • Page 35: Antifreeze

    Table 22 — 50RHR,RVR Coaxial Water Pressure Drop WATER TEMPERATURE (F) UNIT 30 F 50 F 50RHR,RVR Pressure Drop (psi) 006* 10.5 12.0 11.3 15.0 *Size 006 available in 50RHR unit only. Table 23 — 50RHS,RVS,RDS Coaxial Water Pressure Drop WATER TEMPERATURE (F) UNIT 30 F...
  • Page 36: Cooling Tower/Boiler Systems

    Cooling Tower/Boiler Systems — ically use a common loop temperature maintained at 60 to 90 F. Carrier recommends using a closed circuit evaporative cooling tower with a secondary heat exchanger between the tower and the water loop. If an open type cooling tower is used continu- ously, chemical treatment and filtering will be necessary.
  • Page 37: Units With Hwr Option

    compressor application, all compressor relays and related func- tions will track with their associated DIP switch 2 on S1. NIGHT LOW LIMIT (NLL) STAGED HEATING — In NLL staged Heating mode, the override (OVR) input becomes active and is recognized as a call for heating and the control will immediately go into a Heating Stage 1 mode.
  • Page 38: Aquazone Deluxe D Control Led Indicators

    Aquazone™ Deluxe D Control LED Indica- There are 3 LED indicators on the Deluxe D Control: tors — STATUS LED — Status LED indicates the current status or mode of the Deluxe D control. The Status LED light is green. TEST LED —...
  • Page 39: Compressor

    Proper water treatment can minimize tube fouling and pitting. If such conditions are anticipated, water treatment analysis is recommended. Refer to the Carrier System Design Manual, Part 5, for general water conditioning information. Follow all safety codes. Wear safety glasses and rubber gloves when using inhibited hydrochloric acid solution.
  • Page 40: Refrigerant Charging

    Refrigerant Charging To prevent personal injury, wear safety glasses and gloves when handling refrigerant. Do not overcharge system — this can cause compressor flooding. NOTE: Do not vent or depressurize unit refrigerant to atmosphere. Remove and reclaim refrigerant following accepted practices. Air Coil Fan Motor Removal Before attempting to remove fan motors or motor mounts, place a piece of plywood over evaporator coils to prevent...
  • Page 41 Ensure thermostat set for heating or cooling operation. Unit locked out Check for lockout codes. Reset power. Compressor overload Check compressor overload. Replace if necessary. Thermostat wiring Check Y and W wiring at heat pump. Jumper Y and R for compressor operation in Test mode. SOLUTION...
  • Page 42 Fan motor Check for line voltage at motor. Check capacitor. Thermostat wiring Check Y and W wiring at heat pump. Jumper Y and R for compressor operation in test mode. Reversing valve Set for cooling demand and check 24 VAC on RV coil and at control.
  • Page 43: 50Rhc,Rvc,Rhr,Rhs,Rvr,Rvs,Rds Start-Up Checklist

    CUSTOMER:___________________________ MODEL NO.:___________________________ I. PRE-START-UP DOES THE UNIT VOLTAGE CORRESPOND WITH THE SUPPLY VOLTAGE AVAILABLE? (Y/N) HAVE THE POWER AND CONTROL WIRING CONNECTIONS BEEN MADE AND TERMINALS TIGHT? (Y/N) HAVE WATER CONNECTIONS BEEN MADE AND IS FLUID AVAILABLE AT HEAT EXCHANGER? (Y/N) HAS PUMP BEEN TURNED ON AND ARE ISOLATION VALVES OPEN? (Y/N) HAS CONDENSATE CONNECTION BEEN MADE AND IS A TRAP INSTALLED? (Y/N)
  • Page 44 SUBCOOLING = DISCHARGE SATURATION TEMPERATURE – LIQUID LINE TEMPERATURE (DEG F) *Use 500 for water, 485 for antifreeze. Copyright 2007 Carrier Corporation Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Book 1 Catalog No.

Table of Contents