Installation; Control Configuration With The Desuperheater Option; Operating Limits - Carrier AquaSnap Touch Pilot Junior Series Installation, Operation And Maintenance Instructions

Reversible air-to-water heat pumps
Table of Contents

Advertisement

18 - PARTIAL HEAT RECLAIM USING DESUPER-HEATERS (OPTION 49)

18.3 - Installation

The  water  connections  on  the  desuperheater  water  inlets  and 
outlets must not cause any mechanical local constraint at the heat 
exchangers. If necessary, install flexible connection sleeves.
Install  water  flow  control  and  balancing  valves  at  the  heat 
exchanger outlet.
The volume of the desuperheater circuit water loop must be as 
low as possible so that the temperature can increase rapidly when 
the unit is started up.
The minimum entering water temperature at the desuper-heater 
is 25°C. This requires the use of a three-way valve (item 31 in the 
diagram), with a controller and the sensor controlling the minimum 
required entering water temperature. 
The desuperheater water loop must include a relief valve and an 
expansion tank. When selecting these, consider the water loop 
volume  and  the  maximum  temperature  (90°C)  when  pump 
operation is stopped (item 20 in the diagram).
18.4 - Control configuration with the
desuperheater option
The unit can operate in two modes.
18.4.1 - Efficiency priority mode (standard)
In this mode unit control optimises unit efficiency. Heat reclaim is 
based on the saturated condensing temperature. The percentage 
of the reclaimed heating capacity compared with the total capacity 
rejected by the condenser increases in proportion to the saturated 
condensing temperature. This temperature is directly linked to the 
condenser entering air temperature (entering air temperature in 
cooling mode and water temperature in heating mode).
18.4.2 - Reclaim priority mode
In cooling mode only this configuration allows the user to enter a 
setpoint that is relative to the minimum condensing temperature 
(default = 40°C) to increase the heating capacity reclaimed at the   
desuperheaters, if required. This configuration is only effective if the 
desuperheater  contact  is  activated  on  the  control  board  (user 
connection block). This function is not available for 30RQSY units.
For  setpoint  control  of  the  minimum  saturated  condensing 
temperature and to find the position of the connection block on 
the board refer to the 30RB/RQ Touch Pilot Junior control manual.
Other parameters directly affecting the effective capacity reclaimed 
at the desuperheater are principally: 
• The unit load rates, that decide whether the unit operates 
at full load (100%) or part load.
• The  water  entering  temperature  in  the  desuperheater  as 
well as the condenser entering air temperature.

18.5 - Operating limits

Desuperheater
Entering water temperature at start-up
Leaving water temperature during operation °C
Air condenser
Outside operating temperature
(1)  The entering water temperature at start-up must not be lower than 25°C. For 
installations with a lower temperature a three-way valve is necessary.
Minimum Maximum
°C
25
60
(1)
30
65
Minimum Maximum
°C
-10
46
51

Advertisement

Table of Contents
loading

Table of Contents