Specific Details For Units With A Fan With Available Static Pressure (30Rqsy) - Carrier AquaSnap Touch Pilot Junior Series Installation, Operation And Maintenance Instructions

Reversible air-to-water heat pumps
Table of Contents

Advertisement

17 - SPECIFIC DETAILS FOR UNITS WITH A FAN WITH AVAILABLE STATIC
PRESSURE (30RQSY)
Selection based on the pressure drop
The cooling and heating capacities are given for an available pressure of 160 Pa and for a unit without filter.
To calculate the performances at other pressure drops please use the correction factors below.
■ Cooling mode
Duct pressure drop
0
50
100
130
160
200
240
Duct pressure drop
0
50
100
130
160
180
■ Heating mode
Duct pressure drop
0
50
100
130
160
200
240
Duct pressure drop
0
50
100
130
160
180
Note:
Pressure drop, clean filter = 6 Pa
Pressure drop, dirty filter = 12 Pa
48
30RQSY 039-050/30RQSY 080-120
Fan speed, r/s
12.00
13.33
14.66
15.46
16.26
17.31
18.36
30RQSY 060-078/30RQSY 140-160
Fan speed, r/s
15.83
16.81
17.78
18.36
18.36
18.36
30RQSY 039-050/30RQSY 080-120
Fan speed, r/s
18.36
18.36
18.36
18.36
18.36
18.36
18.36
30RQSY 060-078/30RQSY 140-160
Fan speed, r/s
18.36
18.36
18.36
18.36
18.36
18.36
Power input coefficient
0.943
0.962
0.980
0.990
1.000
1.012
1.023
Power input coefficient
0.929
0.944
0.964
0.978
1.000
1.019
Power input coefficient
0.990
0.990
0.990
1.000
1.000
1.000
1.010
Power input coefficient
1.000
1.000
1.000
1.000
1.000
1.001
Cooling capacity coefficient
1.019
1.012
1.006
1.003
1.000
0.998
0.996
Cooling capacity coefficient
1.018
1.016
1.014
1.011
1.000
0.991
Heating capacity coefficient
1.016
1.012
1.009
1.005
1.000
0.994
0.981
Heating capacity coefficient
1.026
1.020
1.011
1.007
1.000
0.993