ELECTRICAL DATA

208/230-1-60
Maximum
Minimum
OUTDOOR
Overcurrent
UNIT
Circuit
Protection
Ampacity
Ampacity
(MCA)
18K
16
18K HH
16
24K
19
24K HH
20.5
30K
20
30K HH
23
36K
24
36K HH
41
48K
34
48K HH
42
60K
34
60K HH
42
LEGEND
FLA - Full Load Amps
MCA - Minimum Circuit Amps
MOPA - Maximum Overcurrent Protection Ampacity

24V CONNECTION DIAGRAMS

NOTE: Terminal D is now energized when the outdoor unit goes into defrost mode and can be used to enable electric heat. This feature is not
available when the outdoor unit communicates with the indoor unit via non-polarity RS485 Communication S1-S2.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Table 9 — Electrical Data
MAX-MIN
VOLTAGE
RANGE
(MOCP)
20
253-187
20
253-187
30
253-187
35
253-187
35
253-187
35
253-187
40
253-187
50
253-187
50
253-187
50
253-187
60
253-187
60
253-187
Table 10 — Terminal Function
R
C
Y1
Y2
B
W
D
L
COOLING
Running
Power
Power Factor
Current
Consumption
7.5
1620
6.5
1430
9.7
2120
9.4
1920
12.2
2760
12.4
2720
15.82
3750
14.8
3300
21.9
5046
24.2
5530
23.8
5644
26.7
6110
24V Power Connection
Common
Low Demand
High Demand
Heating Reversing Valve
Heating Control
Defrost - (24V output signal)
System Fault - (24V output signal)
16
HEATING
Running
Power
Current Range
Consumption
97.2
6.7
1510
71.5
7
1550
98.9
9.8
2150
94.6
9.13
2040
95.8
12.4
2850
96.4
12.5
2780
97.2
16.12
3496
97.8
14.8
3400
98
23.3
5373
99
21.5
4880
98.3
20.9
4959
97.9
21.5
4940
Power Factor
96.9
71.5
98.8
94.5
96.3
96.7
96.8
97.6
98.4
98.9
97.7
97.1