Grounding The Switch In Other Grounding Environment - H3C S5800 Series Installation Manual

Hide thumbs Also See for S5800 Series:
Table of Contents

Advertisement

WARNING!
Connect the grounding cable to the grounding system in the equipment room. Do not connect it to a fire
main or lightning rod.

Grounding the switch in other grounding environment

If the installation site has no grounding strips, you ground an AC-powered switch through the protective
earth (PE) wire of the power cable, and check that the following conditions are met:
The power cable is a three-wire power cable that provides a PE terminal.
The ground contact in the power outlet is well connected to the ground in the power distribution
room or on the AC transformer side.
The power cable is securely connected to the power outlet.
NOTE:
If the ground contact in the power outlet is not connected to the ground, report the problem and reconstruct
the grounding system.
Figure 43 Ground through the PE wire of an AC power cable
(1) Three-wire AC power cable
NOTE:
To guarantee the grounding effect, use the grounding cable provided with the switch to connect to the
grounding strip in the equipment room as long as possible.
(2) Chassis rear panel
48