Figure 6-1 Shield Connection Using A Clip; Figure 6-2 Bridging Shield Gaps - Siemens SINAMICS GM150 Operating Instructions & Installation Instructions

Medium-voltage drive
Hide thumbs Also See for SINAMICS GM150:
Table of Contents

Advertisement

● Attach the cable shield to a shield busbar directly after the line inlet into the cabinet. Insulate
● Bridge shield gaps (at terminals, circuit-breakers, contactors, etc.) with minimum
SINAMICS GM150 6SL3810-2LN31-8AA2
Operating Instructions Rev.201910281332 EXAMPLE
the shielded cable without any interruptions. Route the cable shield up to the device
connection.
Shield busbar
Shielded cable
Mounting clip
Figure 6-1
Shield connection using a clip
NOTICE
Impaired functionality as a result of damaged or incorrectly connected cable shields
Incorrect connection or damaging of the cable shield can impair the function of the system.
● Handle the cable shield carefully.
● Ensure that the cable shield is correctly connected.
impedance and through the largest possible surface area.
Shield busbars
Cables
Terminals
Figure 6-2
Bridging shield gaps
Electrical connection
6.2 Electromagnetic compatibility
83