Siemens SINAMICS GM150 Operating Instructions & Installation Instructions page 133

Medium-voltage drive
Hide thumbs Also See for SINAMICS GM150:
Table of Contents

Advertisement

3. Press the <▼> function key to select the "AOP diagnostics" row. Press the <OK> function
4. Press the <▲> or <▼> function key to select the desired setting. Press the <OK> function key
* These menus appear only if the "Special access" access level was selected
Software/database version
The following values are displayed:
● Serial number
● MLFB number
● Firmware
● Date/time
● Database
Battery status
This menu shows the charging state of the AOP battery. The battery ensures that the data in
the database and the current time are retained. A battery voltage ≥ 3 V corresponds to 100%
of the battery voltage. A battery voltage ≤ 2 V corresponds to the value 0%. The data is secure
up to a battery voltage of 2 V. Depending on the battery voltage, the following messages are
issued:
● Battery voltage ≤ 2.45 V: "Replace battery".
● Battery voltage ≤ 2.30 V: "Alarm, weak battery".
SINAMICS GM150 6SL3810-2LN31-8AA2
Operating Instructions Rev.201910281332 EXAMPLE
key to confirm the selection.
to confirm the selection.
8.3 Operation via the AOP30 operator panel
Operation
133