Design Of The Basic Line Module; Figure 3-1 Design Of The Power Unit - Siemens SINAMICS GM150 Operating Instructions & Installation Instructions

Medium-voltage drive
Hide thumbs Also See for SINAMICS GM150:
Table of Contents

Advertisement

Description
3.3 Design
The drive is a three-level voltage DC-link drive.
1
2
3
4
Figure 3-1
3.3.2

Design of the Basic Line Module

In a 12-pulse configuration, the Basic Line Module consists of a rectifier module. In a 24-pulse
configuration, the Basic Line Module comprises two rectifier modules.
32
Circuit-breaker
Drive transformer
Basic Line Module
(diode rectifier)
DC link with dry-type capacitors
Design of the power unit
5
Motor Module (3-level inverter) with IGBT
6
Motor-side voltage/current transformers
7
High-voltage motor
SINAMICS GM150 6SL3810-2LN31-8AA2
Operating Instructions Rev.201910281332 EXAMPLE