3.5.2

Power Stack Adapter

The Power Stack Adapter (PSA) acts as the physical interface between the power unit and the
open-loop/closed-loop controller. This is where the galvanic isolation (electrical coupling via
light) between the power unit and the open-loop controller takes place. Data is exchanged
between the Power Stack Adapter and the Control Unit via the DRIVE-CLiQ high-speed serial
communication interface.
Figure 3-4
SINAMICS GM150 6SL3810-2LN31-8AA2
Operating Instructions Rev.201910281332 EXAMPLE
X11 – X14, X21 –
Gating of the power semiconductors, inverter phase u
X24
X15, X16, X25, X26 Gating of the power semiconductors, crowbar
X31 – X34, X41 –
Gating of the the power semiconductors, inverter phase v
X44
X35, X36, X45, X46 Gating of the power semiconductors, braking chopper
X51 – X54, X61 –
Gating of the power semiconductors, inverter phase w
X64
X241, X242
Selecting Safe Torque Off
X70 – X79
Actual value channels 0 to 9
X81
Trip line
X200 – X202
DRIVE-CLiQ interfaces
X231, X232
Analog and digital outputs
S5.0
Switches of the analog inputs, voltage/current measurement AI0
S5.1
Switches of the analog inputs, voltage/current measurement AI1
X221, X222
Analog and digital inputs, temperature sensor connections
LEDs
Diagnostics via LEDs
X210
Electronics power supply
Overview of PSA interfaces
3.5 Description of the components
Description
35