The simulation starts at level = 0, unless a specific level value was entered
beforehand.
2. Press
Holding the key increases (or decreases) the simulated rate of rise (or fall), to 4%
of Span per second.
3. Press
During a measurement or simulation, the DPS300 display responds as though in
the RUN mode, however the value displayed in the Reading field is affected by the
Measurement Parameter selected, and the material level is displayed in the
Auxiliary Reading field.
P920 Reading Measurement
The Reading corresponds to all associated programming.
P921 Material Measurement
The Reading corresponds to the distance between Empty (P006) and the sludge
level.
P922 Space Measurement
The Reading corresponds to the distance between the sludge level and Span
(P007).
P923 Distance Measurement
The Reading corresponds to the distance between the sludge level and the
transducer face.
P924 Volume Measurement
The Reading corresponds to the volume calculation in percent of Max Volume
(P051). Press
P927 Distance Percent
Same as P923, plus alternate reading in % press

Master Reset (P999)

P999 Master Reset
A Global Master Reset (reset all parameters to preset values) should be
performed:
to clear all operator programming from memory.
7ML19981BC01
to switch to the rising (or
to end the simulation, when desired.
as required to display in Max Volume units.
93
for the emptying) simulation as required.
InterRanger DPS300