Independently altered Standard Alarms (P101 to P104), Relay Allocation (P110),
Relay Function (P111) and Relay A/B Setpoints (P112/P113) are automatically
reset when a Relay Set Up value is altered.
Values:
1 = Set Up 1
2 = Set Up 2
3 = Set Up 3
4 = Set Up 4
Standard Alarms (P101 to P104)
In the RUN mode, when the sludge level...
rises to a High or High High Alarm value, the associated Alarm and Relay Status
indicators are displayed and the allocated relay(s) de-energize.
falls 5% of Span (P007) below the High or High High Alarm value, the associated
Alarm and Relay Status indicators extinguish, and the allocated relay(s) energize.
falls below the Low or Low Low Alarm value, the associated Alarm and Relay
Status indicators are displayed and the allocated relay(s) de-energize.
rises 5% of Span (P007) above the Low and Low Low Alarm value, the associated
Alarm and Relay Status indicators extinguish, and the allocated relay(s) energize.
Note:
Enter all Standard Alarm material level values in Units (P005) or percent of Span
(P007) as referenced to Empty (P006).
To display the current value (or enter a new value) in percent of Span, press
as required to display the % symbol.
P101 High Alarm
Enter the High Alarm sludge level for the Point Number displayed.
Values:
P102 Low Alarm
Enter the Low Alarm sludge level for the Point Number displayed.
Values:
P103 High High Alarm
Enter the High High Alarm sludge level for the Point Number displayed, (Relay Set
Up 2 or 4 only).
Values:
7ML19981BC01
-999 to 9999 (preset to 80.00% of Span or equivalent Units)
-999 to 9999 (preset to 20.00% of Span or equivalent Units)
-999 to 9999 (preset to 90.00% of Span or equivalent Units)
59
InterRanger DPS300