If Peripheral Communications (P740) is set for "formatted" messages, a comma is
inserted between each message field (except immediately preceding the "End of
Message" characters).
MT-00 Measurement Message
Start of Message
Field Name
Start Of Message
Message Type
Point #
Reading
Status A
1 character, $0 to $F (convert to binary, e.g. temp, echo, and cable OK, not
priority)
MSB
Status B
1 character, $0 to $F (convert to binary, e.g. scan point is in high alarm)
MSB
7ML19981BC01
Point #
Message type
Definition
STX ($02)
2 characters, 00 (indicates the following data pertains to a
scan point measurement)
3 characters, 001 to 003 (e.g. the message pertains to Point
Number 1)
5 characters, 0.000 to 9999. (e.g. reading = 678.9, DDDD. =
no data, EEEE. = overflow)
LSB
####
1 = temp alarm
1 = loss of echo (failsafe expired)
1 = transducer cable fault
1 = priority point
LSB
####
1 = low low alarm
1 = low alarm
1 = high alarm
1 = high high alarm
99
Status A
Status C
Status B
Reading
Percent
Temperature
End of Message
InterRanger DPS300