Siemens interranger DPS300 Instructional Manual page 80

Table of Contents

Advertisement

"normal"
"formatted"
Note:
Refer to TECHNICAL REFERENCE Communication Support if a Peripheral
Communication is required.
Values:
0 = off
1 = normal messages (preset)
2 = formatted messages
P748 RS485 Termination
Single point termination may be required to minimize transmission reflections, on
long cable runs typical of 500m or more. Turn on the termination if required.
Values:
0 = off
1 = on
P749 Serial Bus Type (V)
Displays the type of communication bus the DPS300 is currently set for. If there is
no connection, the DPS300 defaults to RS-485. If a bus type other than RS-485 is
connected, the DPS300 displays the type of bus it is, or is attempting to,
communicate with.
Displays:
232 = RS-232
485 = RS-485 (default setting when nothing is connected)
bPL = bipolar current loop
rJ11 = for Siemens use
P772 Baud Rate
The communication rate with the master device (i.e
This parameter specifies the rate of communication in Kbaud. Any value may be
entered but only the values shown below are supported.
Note:
This parameter is not reset by P999.
Values:
4.8 = 4800
9.6 = 9600
19.2 = 19 200
38.4 = 38 400 (preset)
InterRanger DPS300
to have messages transmitted in a continuous string of
characters. (Requires less DPS300 processing time than
formatted messages).
to have commas inserted between the message fields for easier
message dissemination (when viewed on a monitor).
80
.
Dolphin Plus on a PC).