Siemens interranger DPS300 Instructional Manual page 23

Table of Contents

Advertisement

P001 = 1
sludge level measured from bottom (see P006)
P002 = 1
primary clarifier
P005 = 1
units in meters
P006 = 4.9,
distance from the face
of the transducer to the
bottom of the clarifier
directly beneath
P110, relay 1 = 1
relay 1 is assigned to
point 1
P111, relay 1 = 50,
relay 1 is assigned for pump control
P112, relay A setpoint = 0.3
sludge level at which the pump turns on
P113, relay B setpoint = 0.1
sludge level at which the pump turns off
7ML19981BC01
P006 =
4.9 m
23
P112 =0.3 m,
pump on
P112 =0.1 m,
pump off
InterRanger DPS300

Advertisement

Table of Contents
loading

Table of Contents