Insert New Switching Time - ABB i-bus EIB Product Manual

Application unit time, intelligent installation systems
Hide thumbs Also See for i-bus EIB:
Table of Contents

Advertisement

®
ABB i-bus
EIB / KNX
3.4.4.1

Insert new switching time

© 2006 ABB STOTZ-KONTAKT GmbH
Commissioning
Note
Before a switching time is inserted, a day routine must have
been created under Day routines.
Fig. 64:
Dialog window: "Insert switching time"
To insert a switching time, first select Time switch program, Day routines in
the selection area followed by a day routine, e.g. 01: Normal weekday.
The associated table is activated in the right-hand window.
The table is divided into Time, GA No., GA Name, Value, Type and SoC.
The meaning of the individual columns is as follows:
Time
This column displays the set switching time at which a telegram is sent.
GA No.
The number of the group address is the unique identifier of a group address.
GA Name
The name of the group address is displayed here.
Value
This column displays which value is sent with the group address.
59