Commissioning; Overview; Functions Of The Application Program - ABB i-bus EIB Product Manual

Application unit time, intelligent installation systems
Hide thumbs Also See for i-bus EIB:
Table of Contents

Advertisement

®
ABB i-bus
EIB / KNX
3

Commissioning

3.1

Overview

© 2006 ABB STOTZ-KONTAKT GmbH
Commissioning
The application program "Times Groups/2" is available for the Application
Unit Time. Programming requires ETS3. A maximum of 250 communication
objects, 250 group addresses and 254 associations can be linked.
The following functions are available:
Time switch program
Defines when telegrams with specific group addresses and values
are sent on the bus.
Day routines
Contains the time program of a day from 00:00 to 23:59. Day
routines can be activated and deactivated by the time switch
program and by telegrams. There are 15 day routines available.
Switching times
Up to 800 switching times can be assigned to the day routines.
Week routine
Defines the assignment of day routines to the days of the week.
There is one week routine available.
Special days
Special days denote individual days or time intervals which
deviate from the standard week routine. There are 100 special
days available.
Daylight saving times
Automatic calculation of the daylight saving times. A total of 10
consecutive years can be calculated.
Group
A combination of group addresses which are sent at the same
time. There are 30 groups available.
Group members
Group addresses which belong to a group. There are 300 group
members available.
Group triggers
Group addresses which trigger a group. The type and value of the
group address determine the triggering of the group e.g.:
Table 3:

Functions of the application program

"0" switches ON,
"1" switches OFF,
"Value < 230" switches ON,
"Value > 250" switches OFF.
12

Advertisement

Table of Contents
loading

This manual is also suitable for:

I-bus abz/s 2.1I-bus knx

Table of Contents