Commissioning
Time frame, from, to
The date for the Time frame from ... can be set in the range between
1.1.2000 and 31.12. 2035. The representation is in numbers which are
separated by full stops in the sequence Day. Month. Year. Entries for the
year in the range 36...99 are rejected. To the right of the input field for the
date, there is a button with which the calendar for the current date can be
displayed. The input of the date for the start and end can be carried out via
the selection of a date in the calendar or through the direct input of the date.
The meaning of the individual columns is as follows:
Date
This column displays the date when a telegram is sent for the selected group
address.
Time
This column displays the time at which a telegram is sent for the selected
group address.
Value
This column displays the value which is sent with this telegram for the
selected group address e.g. switching the light on or off.
SoC (Send on Change)
A tick in the SoC column indicates that a telegram is only sent if the value
differs from the last value that was sent e.g. if the light should be switched
on and is already switched on, this telegram is not sent.
by day routine
This column displays which switching time is assigned to this day routine for
the selected group address.