Parameters; General - ABB i-bus EIB Product Manual

Application unit time, intelligent installation systems
Hide thumbs Also See for i-bus EIB:
Table of Contents

Advertisement

®
ABB i-bus
EIB / KNX
3.4

Parameters

3.4.1

General

© 2006 ABB STOTZ-KONTAKT GmbH
Commissioning
Fig. 28:
Parameter window: "General"
The general parameters are shown in the right-hand window.
Inactive time (mm:ss)
Options:
(mm)
(ss)
This parameter sets the Inactive time on bus voltage recovery and during a
download. During this period, no telegrams are sent and any received
telegrams are not evaluated. The displays for minutes and seconds can be
edited separately via the Left arrow and Right arrow buttons.
Min. telegram interval
Options:
normal / 0.1 s / 0.2 s / 0.3 s / 0.4 s / 0.5 s
The parameter Min. telegram interval sets at which minimum intervals the
Application Unit Time should send telegrams in sequence.
The option normal means that no delay is inserted.
An example:
If a Min. telegram interval of 0.5 s is set and 5 telegrams should be sent, the
last telegram is sent 2.5 s after the first telegram.
00...59
00...59
31