Samsung DVM PLUS III Technical Data Book page 735

Hide thumbs Also See for DVM PLUS III:
Table of Contents

Advertisement

06_Installation(02~45)
3/15/08 4:34
No.
Error code
30
E-201
31
E-202
32
E-203
33
E-204
34
E-210
35
E-211
35
E-213
35
E-214
36
E-215
37
E-216
38
E-217
39
E-218
40
E-221
41
E-226
42
E-231
43
E-236
44
E-237
45
E-241
46
E-246
47
E-251
48
E-256
49
E-257
50
E-258
51
E-261
52
E-262
53
E-263
54
E-264
55
E-265
56
E-266
57
E-267
58
E-268
58
E-269
59
E-271
60
E-276
61
E-277
62
E-278
63
E-291
64
E-296
65
E-307
66
E-308
67
E-311
68
E-312
69
E-321
70
E-322
Page 33
Communication error between indoor and outdoor unit
(Tracking failure or the setting quantity of indoor unit on outdoor unit's PCB differs from the quantity of installed indoor unit.)
Communication error between indoor and outdoor unit. (After tracking is completed, and then no response from indoor unit)
Communication error between main and sub outdoor unit
The setting quantity of MCU on outdoor unit's PCB differs from the quantity of installed MCU.
Communication error between MCU and outdoor unit.
Indoor unit's address overlapped on the MCU.
No matching between installed indoor unit's address and indoor unit's address on the MCU.
Setting error of MCU's quantity in outdoor unit's PCB
Indoor unit's address setting error on the MCU. (There is same address among the MCUs)
Setting error of indoor unit activating dip switch on MCU's PCB.
(The indoor unit is not connected with the MCU's port but indoor unit activating dip switch on MCU's PCB turns on.)
Setting error of indoor unit activating dip switch on MCU's PCB.
(The indoor unit is connected with the MCU's port but indoor unit activating dip switch on MCU's PCB turns off.)
Setting error of indoor unit's quantity on MCU's PCB.
(The quantity of installed indoor units exceeds the setting number of the MCU's PCB.)
Ambient air temperature sensor of outdoor unit. (Open or Short)
Ambient air temperature sensor is detached from outdoor unit.
Cond_out temperature sensor of main outdoor unit. (Open or Short)
Cond_out temperature sensor of the outdoor unit. (Open or Short)
Cond temperature sensor of outdoor unit. (Open or Short)
Cond_mid temperature sensor is detached from sensor hold of the pipe.
Cond_out 1 temperature sensor is detached from sensor hold of the pipe.
Discharge temperature sensor of compressor 1. (Open or Short)
Discharge temperature sensor of compressor 1. (Open or Short)
Discharge temperature sensor of compressor 2. (Open or Short)
Discharge temperature sensor of compressor 3. (Open or Short)
Discharge temperature sensor of compressor 1 is detached from the sensor hold of the pipe.
Discharge temperature sensor of compressor 1 is detached from the sensor hold of the pipe.
Discharge temperature sensor of compressor 2 is detached from the sensor hold of the pipe.
Discharge temperature sensor of compressor 3 compressor is detached from the sensor hold of the pipe.
Sump(Base) temperature sensor of main unit's compressor is detached from the base of the compressor.
Sump(Base) temperature sensor of sub1 unit's compressor is detached from the base of the compressor.
Sump(Base) temperature sensor of sub2 unit's compressor is detached from the base of the compressor.
Sump(Base) temperature sensor of sub3 unit's compressor is detached from the base of the compressor.
Suction temperature sensor is detached from the sensor hold of the pipe.
Sump(Base) temperature sensor of compressor 1. (Open or Short)
Sump(Base) temperature sensor of compressor 1. (Open or Short)
Sump(Base) temperature sensor of compressor 2. (Open or Short)
Sump(Base) temperature sensor of compressor 3. (Open or Short)
High pressure sensor. (Open or Short)
Low pressure sensor. (Open or Short)
Oil balance temperature sensor. (Open or Short)
Suction temperature sensor. (Open or Short)
Double tube / Liquid temperature sensor. (Open or Short)
Main cooling solenoid valve opening error.
EVI_in temperature sensor. (Open or Short)
EVI_out temperature sensor. (Open or Short)
Description