05-1_control systems(002~045)
Error code
Display a type of error occurred in indoor units, outdoor units and, wired remote controller.
(The following is errors related to a wired remote controller)
Error code
601
602
603
604
605
606
607
618
619
620
621
653
654
3/15/08 4:09
Page 27
Description
Wired remote controller
Indoor unit communication error
Wired remote controller communication error between
Master
Slave
Communication packet error
Wired remote controller
Indoor unit tracking failure error
Wired remote controller
7-day scheduler communication
error
COM1, COM2 cross installation error
2 Master wired remote controllers
Excessive number of indoor units installation error
Multiple Celsius / Fahrenheit indoor unit error
Celsius / Fahrenheit setting error
Option switch setting error of the Master/Slave wired remote
controller
Wired remote controller (MWR- WS00)temperature sensor error
(Short/Open)
EEPROM error
Remark
When communication with indoor units is blocked for
3 minutes.
When two wired remote controllers are used for one
indoor unit, communication between has been blocked.
-
Occurs when an indoor unit is not installed.
When communication with 7-day scheduler is
blocked for 3 minutes.
When the wired remote controller is installed onto
indoor unit COM1 (F1/F2).
When two Master wired remote controllers are
installed in one COM2 communication line.
When more than 16 indoor units are connected to
wired remote controller.
When indoor units set in Celsius or Fahrenheit are
together connected to the wired remote controller.
When indoor unit is set in Celsius, its wired remote
controller is set to Fahrenheit, or vise versa.
-
-
-
V-27