Samsung DVM PLUS III Technical Data Book page 592

Hide thumbs Also See for DVM PLUS III:
Table of Contents

Advertisement

05-2_control systems(046~081)
Control Systems
2
Centralized control system
2
2-2. Centralized controller (MCM-A202A)
8) Option switch K3 – Tracking mode setting
DMS
S-NET mini
Function controller
S-NET
II
Plus
V-60
3/6/08 14:02
Page 60
Group mode – Indoor unit control/monitoring with the RMC address
Room mode - Indoor unit control/monitoring with the Main address
Interface with DMS and S-NET mini – Set K4 to the OFF position
DMS
Centralized controller
S-NET mini
( K4=OFF)
K3=OFF
Group mode
Group mode
K3=ON
Room mode
Group mode
K3=OFF
Group mode
Room mode
K3=ON
Room mode
Room mode
Interface with S-NET II Plus – Set K4 to the ON position
Centralized controller
S-NET
II Plus
( K4=ON)
K3=OFF
Group mode
Group mode
K3=ON
Group mode
Room mode
K3=OFF
Room mode
Group mode
K3=ON
Room mode
Room mode
❈ S-NET II Plus does not support MIM-B13A interface.
Interface with function controller – Set K4 to the ON position
Centralized controller
Function controller
( K4=ON)
K3=Not used
Group mode
❈ Function controller controls indoor units based on their RMC address.
Room mode is not supported for interface with the function controller.
Main:0
Main:1
RMC:3
RMC:4
DMS, S-NET mini
Centralized controller
operation
operation
Control/monitoring by
• On/Off control by RMC 3,4,5
RMC 3,4,5
• Indoor unit LED display
• All ON LED display
Control/monitoring by
• Indoor unit control not allowed
RMC 3,4,5
• Indoor unit LED OFF
• All ON LED display
Control/monitoring by
• On/Off control by RMC 3,4,5
Main 0,1,2
• Indoor unit LED display
• All ON LED display
Control/monitoring by
• Indoor unit control not allowed
Main 0,1,2
• Indoor unit LED OFF
• All ON LED display
II
Centralized controller
S-NET
Plus
operation
operation
• On/Off control by RMC 3,4,5
Control/monitoring by
• Indoor unit LED display
RMC 3,4,5
• All ON LED display
Control/monitoring by
• Tracking mode setting error
• LED 4,5,6,7 ➔ Rotating display
RMC 3,4,5
Control/monitoring by
• Tracking mode setting error
• LED 0,1,2,3 ➔ Rotating display
Main 0,1,2
• Indoor unit control not allowed
Control/monitoring by
• Indoor unit LED OFF
Main 0,1,2
• All ON LED display
Function controller
Centralized controller
operation
operation
• On/Off control by RMC 3,4,5
Control/monitoring by
• Indoor unit LED display
RMC 3,4,5
• All ON LED display
Main:2
RMC:5