3-1.DVM,HR3_Outdoor(238~293)
Outdoor Units
1
DVM PLUS III, DVM PLUS III HR
1
1-8. Operation limit
1) Cooling
50
45
40
35
30
25
20
15
10
5
0
-5
10
15
20
Indoor temperature(ºCWB)
1-9. Cycle operation mode
1) Description of cycle function parts
No Classification
1
A
DVI (Digital Vapor Injection) compressor
2
B
FVI (Fixed Vapor Injection) compressor 1
3
C
FVI (Fixed Vapor Injection) compressor 2
4
D
PWM solenoid valve
5
E
Discharge temperature sensor of DVI compressor
6
F
Discharge temperature sensor of FVI compressor 1
7
G
Discharge temperature sensor of FVI compressor 2
8
H
Oil separator
9
I
Capillary tube from oil separator
10
J
High pressure switch
11
K
Hot gas bypass solenoid valve
12
L
Check valve
13
M
High pressure sensor
14
N
Reversing solenoid valve (4way valve)
15
O
Heat exchanger of outdoor unit (Condensing unit)
16
P
Ambient air temperature sensor
17
Q
Cond_out temperature sensor
18
R
Main EEV 1 ( For heating operation)
III-274
3/21/08 11:21
Page 274
25
30
Description
2) Heating
25
20
15
10
5
Range for
continuous
0
operation
-5
-10
-15
-20
10
15
20
25
30
Indoor temperature(ºCDB)
No Classification
19
S
Main EEV 2 ( For heating operation)
20
T
Check valve
21
U
Liquid bypass solenoid valve
22
V
EVI EEV
23
W
Turbo Intercooler
24
X
EVI_in temperature sensor
25
Y
EVI_out temperature sensor
26
Z
Liquid tube temperature sensor
27
a
EVI bypass pilot solenoid valve
28
b
Suction temperature sensor
29
c
Accumulator
30
d
Accumulator CCH (Crank Case Heater)
31
e
Oil solenoid valve 1
32
f
Oil solenoid valve 2
33
g
Oil solenoid valve 3
34
h
Oil balancing service valve between units
35
i
Low pressure sensor
36
j
Check valve
Description