Samsung DVM PLUS III Technical Data Book page 552

Hide thumbs Also See for DVM PLUS III:
Table of Contents

Advertisement

05-1_control systems(002~045)
Control Systems
1
Individual control system
1
1-3. Wired remote controller
2) MWR-WS00
(4) Additional functions
Service mode menu description
Menu
V-20
3/15/08 4:09
Page 20
Detailed description
SW 8 OFF : Monitor the compensation value of the temperature
sensor in the wired remote controller
SW 8 ON : Set the compensation value for temperature sensor in
the wired remote controller.
Compensate temperature sensor for wired remote controller:
To compensate and display the measured temperature on the
temperature sensor in the wired remote controller.
(ex : Actually measured temperature 20°,
and compensate 5° → It is displayed as 25° when indoor
temperature is displayed).
SW 8 OFF : Monitor whether indoor unit's FAN RPM
compensation is used
SW 8 ON : Set indoor unit FAN RPM compensation
Compensation of FAN RPM of the indoor unit:
A function to increase the FAN RPM in the indoor unit
(ex : When compensation is set, RPM is changed from low to
medium.)
0 : Use the default RPM of the indoor unit
(Use the indoor unit PCB switch setting as it is.)
1 : Set indoor unit RPM 1 level Up compensation.
2 : Cancel indoor unit RPM compensation.
SW 8 OFF : Monitor the EEV step for the stopped indoor unit
under the Heating mode.
SW 8 ON : Set the EEV step for the stopped indoor unit under the
Heating mode.
0 : Use the default setting for indoor units
(Use the default setting for indoor unit PCB switch).
1 : Fixed step to 0 or 80.
2 : Fixed step to 80.
SW 8 OFF : Monitor the filter replacement time
SW 8 ON : Set the filter replacement time
Filter replacement time:
Set the indoor unit filter replacement time.
0000 : Use the default setting for indoor units.
(Use the default setting for indoor unit PCB switch.)
1000 : Replacement display after 1000 hours.
2000 : Replacement display after 2000 hours.
Display
Temperature compensation value
(-9~9°)
RPM compensation /
no compensation display
Setting value of the EEV step for the
stopped indoor unit during heating
Filter replacement notice time setting

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Dvm plus iii hrMini dvm

Table of Contents