Samsung DVM PLUS III Technical Data Book page 727

Hide thumbs Also See for DVM PLUS III:
Table of Contents

Advertisement

06_Installation(02~45)
3/15/08 4:34
DVM PLUS III HR
12Hp
14Hp
16Hp
(E)
(A1)
(A1)
(A3)
(A2)
(A1)
(F)
(D)
(A)
(B)
❈ Example) 42HP of compact
combinations
Pipe size(O. D.mm)
HP
Mark
Low
Liquid
gas
12 HP (A1) ø12.70 ø25.40 ø22.23
14 HP (A1) ø12.70 ø25.40 ø22.23
16 HP (A1) ø12.70 ø28.58 ø22.23
26 HP (A2) ø19.05 ø31.75 ø28.58
42 HP (A3) ø19.05 ø38.10 ø31.75
Page 25
Outdoor unit connection pipe size : (A1), (A2), (A3)
A1 : Select the pipes according to the outdoor unit
capacity with following table.
A2 : Select the pipes according to sum of outdoor
unit capacities behind the outdoor joint with
following table.
A3 : Select the main pipe of outdoor units with the
following table.
(B)
Pipe size (O.D. mm), (A)
Outdoor
Liquid
unit
pipe
pipe
8HP
ø19.05
ø9.52
10HP
ø22.23
(C)
12HP
ø25.40
14HP
ø12.70
16HP
18HP
ø28.58
20HP
High
ø15.88
22HP
gas
24HP
26~30HP
ø31.75
32~34HP
ø19.05
36~48HP
ø38.10
50~64HP
ø22.23
ø44.45
*A1 : Pipes to the outdoor unit (Liquid, Gas, High pressure gas)
*A2 : Pipes between outdoor joint kits (Liquid, Gas, High pressure gas)
*A3 : Main pipes (Liquid, Gas, High pressure gas)
Pipe size between branch joints : (B)
Select the pipe size according to the capacity sum of
indoor units which are air connected below this pipe.
Total indoor unit's capacity
15.0 kW and below
Over 15.0~23.2 kW and below
Over 23.2~29.0 kW and below
Over 29.0~40.6 kW and below
Over 40.6~46.4 kW and below
Over 46.4~69.6 kW and below ø15.88
Over 69.6~98.6 kW and below
Over 98.6~139.2 kW and below
Over 139.2 kW
Pipe size between branch joints and indoor unit (C)
Select the pipe size according to the indoor's capacity.
Indoor unit's
capacity
Liquid pipe
2.2~5.6 kW
ø6.35
7.1~14.0 kW
ø9.52
■ Branch joint of outdoor unit's multi connection (D)
Low gas pipe
High gas pipe
Oil
Gas
High
balancing
■ First branch joint (E)
pipe size
gas pipe
Select branch joint according to outdoor unit's capacity
ø15.88
ø19.05
Liquid & Low
ø22.23
pressure gas
ø6.35
ø25.40
ø28.58
pressure gas
ø31.75
ø38.10
■ Branch joint (F)
Liquid &
low
Pipe size (O.D. mm)
pressure
Liquid
Gas
High
gas
pipe
pipe
gas pipe
Y-joint
ø15.88
ø15.88
ø9.52
ø19.05
ø22.23 ø19.05
ø25.40
ø12.70
ø22.23
High
ø28.58
pressure
ø25.40
gas
ø31.75 ø28.58
Y-joint
ø19.05
ø38.10 ø31.75
ø22.23 ø44.45 ø38.10
Pipe size (O.D. mm)
Gas pipe
ø12.70
ø15.88
Branch joint : (D), (E), (F)
Model
Capacity of outdoor unit
MXJ-T3819K
Below 48 HP
Liquid &
MXJ-T4422K
Above 50 HP
MXJ-T3100K
Below 48 HP
MXJ-T3800K
Above 50 HP
Outdoor unit
8, 10, 12, 14 HP
MXJ-YA2512K
16 HP
MXJ-YA2812K
18, 20, 22, 24HP
MXJ-YA2815K
Y-joint
26, 28, 30, 32, 34HP
MXJ-YA3119K
(E)
36, 28, 40, 42, 44, 46, 48HP MXJ-YA3819K
50HP~
MXJ-YA4422K
Outdoor unit
High
8 HP
MXJ-YA1500K
10 ~ 24 HP
MXJ-YA2500K
Y-joint
26 ~ 48 HP
MXJ-YA3100K
(E)
50HP ~
MXJ-YA3800K
Model
Total indoor unit' capacity
MXJ-YA1509K
15.0 kW and below
MXJ-YA2512K
Over 15.0 ~ 40.6 kW and below
MXJ-YA2812K
Over 40.6 ~ 46.4 kW and below
MXJ-YA2815K
Over 46.4 ~ 69.6 kW and below
MXJ-YA3119K
Over 69.6 ~ 98.6 kW and below
(F)
MXJ-YA3819K Over 98.6 ~ 139.2 kW and below
MXJ-YA4422K
Over 139.2 kW
Model
Total indoor unit' capacity
MXJ-YA1500K
23.2 kW and below
MXJ-YA2500K
Over 23.2 ~ 69.6 kW and below
MXJ-YA3100K Over 69.6 ~ 139.2 kW and below
(F)
MXJ-YA3800K
Over 139.2 kW
Model
Model
VI-25