1. products(01~41)
3/14/08 22:01
Products
5
DVM design process
5
5-2. DVM design process example (Cooling)
H2
H1
❈ Piping length : L + [the longest pipe out of (A, B, C, D)]
Piping height : The highest pipe out of (H1, H2, H3, H4)
Maximum level difference : H4
5) Calculate the actual capacity of each outdoor unit
The actual capacity of each outdoor unit is as follows:
Actual capacity of outdoor unit x
❈ The actual capacity of outdoor unit : 47.5kW
The sum of capacity of all indoor units: 52.9kW
Zone A : AVXWVH036 ➟ 47.5kW x 3.6kW/52.9kW = 3.23kW
Zone B : AVXDSH071 ➟ 47.5kW x 7.1kW/52.9kW = 6.38kW
Zone C : AVXCMH056 ➟ 47.5kW x 5.6kW/52.9kW = 5.03kW
Zone D : AVXC4H071 ➟ 47.5kW x 7.1kW/52.9kW = 6.38kW
Zone E : AVXDSH112 ➟ 47.5kW x 11.2kW/52.9kW = 10.06kW
Zone F : AVXFHT071 ➟ 47.5kW x 7.1kW/52.9kW = 6.38kW
Zone G : AVXC4H112 ➟ 47.5kW x 11.2kW/52.9kW = 10.06kW
I-38
Page 38
H4
H3
L
Each indoor unit capacity
the sum of capacity of all indoor units