3-2.mini_Outdoor unit(294~321)
Outdoor Units
2
Mini DVM
2
2-1. Specifications
Type
Model
Power Supply
Mode*
1)
Performance
Horse Power
Capacity
Cooling*
Heating*
Power
Nominal input
Cooling
Heating
Cooling
Nominal running
current
Heating
Circuit Breaker (MCCB/ELB)
COP
Cooling
Heating
Sound Pressure*
4)
Cooling
Sound
Heating
Sound Power
Cooling
Heating
Compressor
Model
Type
Piston Displacement
Output
Lubricant
Type
Charging
Type
Refrigerant
Factory Charging
Type/Control
Fan
Motor Output
Airflow Rate
External Static Pressure (Max.)
Piping
Liquid (Flare)
Connections
Gas (Flare)
Installation Limitation
Max. Length
Max. Height
Set Size
Net Weight
Shipping Weight
Net Dimensions (WxHxD)
Shipping Dimensions (WxHxD)
Main Power (Below 20m/Over 20m)
Cable
Communication
Cooling
Operating
Heating
Temp.
Standard Accessories
*1) Mode
- HP : Heat Pump, HR : Heat Recovery
*2) Nominal cooling capacities are based on;
- Indoor temperature : 27°C DB, 19°C WB
- Outdoor temperature : 35°C DB, 24°C WB, Equivalent piping length : 7.5m, Level differences : 0m
*3) Nominal heating capacities are based on;
- Indoor temperature : 20°C DB, 15°C WB
- Outdoor temperature : 7°C DB, 6°C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.
III-294
3/15/08 4:06
Page 294
RVXMHF040EA
ø/V/Hz
1/220~240/50
-
HP
HP
4
kW
2)
12.5
Btu/h
42,700
3)
kW
14.5
Btu/h
49,400
kW
3.75
kW
3.58
A
19.0
A
18.0
A
30
-
3.33
-
3.91
dB(A)
55
dB(A)
56
dB(A)
-
dB(A)
-
-
ZRD61KC-PFZ
-
Digital scroll
cc/Rev
58.10
kW
-
-
3MAF POE
kg
1893
-
R410A
kg
5.5
-
Propeller/TAB
W
200X2
m
3
/min
105
Pa(mmAq)
-
ø, mm
9.52
ø, mm
15.88
m
100
m
30
kg
124
kg
132
mm
932X1,128X375
mm
1,286X1,091X472
mm
2
6.0/8.0
mm
2
0.75~1.5
°C
-5 ~ 43
°C
-20 ~ 24
-
-
RVXMHF050EA
RVXMHF050GA
1/220~240/50
3/380~415/50
HP
HP
5
5
14.0
14.0
47,800
47,800
16.0
16.0
54,600
54,600
4.61
4.61
4.13
4.13
22.4
8.5
20.1
7.8
30
20
3.04
3.04
3.87
3.87
55
55
57
57
-
-
-
-
ZPD67KCE-PFZ
ZPD72KCE-TFD
Digital scroll
Digital scroll
62.98
67.13
-
-
3MAF POE
3MAF POE
1893
1893
R410A
R410A
5.5
5.5
Propeller/TAB
Propeller/TAB
200X2
200X2
105
105
-
-
9.52
9.52
15.88
15.88
100
100
30
30
125
125
133
133
932X1,128X375
932X1,128X375
1,286X1,091X472
1,286X1,091X472
6.0/8.0
4.0/6.0
0.75~1.5
0.75~1.5
-5 ~ 43
-5 ~ 43
-20 ~ 24
-20 ~ 24
-
-
RVXMHF060GA
3/380~415/50
HP
6
16.0
54,600
18.0
61,500
5.24
4.82
11.0
9.9
20
3.05
3.73
57
60
-
-
ZPD83KCE-TFD
Digital scroll
77.20
-
3MAF POE
1774
R410A
5.5
Propeller/TAB
200X2
105
-
9.52
19.05
100
30
125
133
932X1,128X375
1,286X1,091X472
4.0/6.0
0.75~1.5
-5 ~ 43
-20 ~ 24
-