Samsung DVM PLUS III Technical Data Book page 709

Hide thumbs Also See for DVM PLUS III:
Table of Contents

Advertisement

06_Installation(02~45)
3/15/08 4:34
Oil trap
Max. piping length
Allowable pipe length
from the first branch to
the farthest indoor unit
High pressure gas pipe
connection for HR
outdoor modules
(HR only)
New
additional joints
High pressure gas
connection for HR MCU
(HR only)
MCU
(HR system)
Additional refrigerant
charging
(HR system)
Maximum connectable
indoor units
Interface module
Ex) 12HP
MCCB, ELB,
Power cable
Connectable indoor units
❈ For more detail information about installation, refer to installation manual.
Page 7
DVM PLUS III, DVM PLUS III HR
Less than 1m
2m or more
• When the piping length between the outdoor
units is 2m or more, a vertical trap has to be
installed like above diagram.
200m
90m
(If the pipe length between the first branch to the farthest indoor unit
is over 45 m, the pipe size has to be increased 1size.)
Type
Model
MXJ-T3100K
Outdoor joint
MXJ-T3800K
Type
Outdoor joint
MXJ-T4422K
Y-joint
MXJ-YA2812K
Y-joint (Optional products)
❈ Model: MXJ-YA1500/YA2500
MXJ-YA3100/YA3800
◆ High pressure gas pipe : brazing type
Additional Refrigerant Charging of MCU Kit
Additional refrigerant charging of MCU is
0.5kg for every MCU kit.
64 indoor units
MIM-B13A
HP
MCCB(A)
12
40
40A, 30mA, 0.1second or less
AVX✳✳✳000EE
200~300mm
Outdoor unit capacity
below 48HP
Above 50Hp
Model
MCU-4EAE1
MCU-4EAEV1
MCU-6EAE1
◆ High pressure gas pipe : Flare type
(kg/unit)
0.5
Ex) 12HP
ELB
HP
12
DVM PLUS II, DVM HR II
No vertical trap
No vertical trap
170m
45m
-
-
T-joint (Field available)
MCU-4EAE
MCU-4EAEV
MCU-6EAE
-
48 indoor units
MIM-B13
MCCB(A)
ELB
35
40A, 30mA, 0.1second or less
AVX✳✳✳000EA, EB,EC
VI-7