Samsung DVM PLUS III Technical Data Book page 132

Hide thumbs Also See for DVM PLUS III:
Table of Contents

Advertisement

chapter2_Indoor units(052~107)
Indoor Units
7
Console
7
7-5. PCB connector lay-out
Main PCB
1
2
17
16
15
14
13
12
No.
CN # COLOR
1
CN33
Blue
2
CN31
Red
3
CN32
White
4
CN45
Yellow
5
CN86
Black
6
CN73
White
7
CN100
Blue
8
CN70
White
9
CN75
Black
10
CN42
White
11
CN41
White
12
CN83
White
13
CN81
White
14
CN20
White
15
CN10
Black
16
CN82
Yellow
17
CN85
Blue
18
CN87
Blue
No.
CN # COLOR
19
CN61
Black
20
CN83
White
II-92
3/14/08 22:15
Page 92
5
3
4
11
10
18
Main PCB
FUNCTION
Communication with Wired Remote
Controller (COM2)
Communication with Outdoor Units (COM1)
DC12V for Wired Remote Controller
MPI
Main-Sub PCB connector
Fan Motor
AC 230V Input
Earth
Ventilator
Eva-Out Sensor
Room Sensor, Eva-In Sensor
Main-Display PCB connector
Louver Motor
MICOM Download 2
MICOM Download 1
Damper Motor
EEV
Main-Damper PCB connector
Sub PCB
FUNCTION
Main-Sub PCB connector
External Contact Control
7
6
8
9
No.
S/W
A
SW01
SW02
B
SW03
SW04
No. S/W
FUNCTION
K1
K2
Centralized Controller
K3
RPM Up
K4
Optional Drain Pump
K5
Heating Thermo-off
K6
Filter Signal Display
C
K7
Hot Water Coil
K8
Electrical Heater
K9 Min. EEV Step at Heating Fixed 80 step 0 or 80 step
Pri o ri t y of Indoor uni t Di s pl a y
K10
on Wired Remote Controller (Default)
K11 External Contact Control
K12
Sub PCB
A
20
19
B
C
FUNCTION
Main Address Setting
(00~63)
SW03
SW04
Address of
Group Address
Interface
(RMC) for
Module
Centralized
Channel 0~2
Control 0~F
ON
OFF
-
-
-
Not use
Use
N/A
N/A
N/A
N/A
+2°C
+5°C
1,000hrs
2,000hrs
N/A
N/A
N/A
N/A
Slave
Master
Not use
Use
-
-
-