Advertisement

06_Installation(02~45)
3/15/08 4:34
K4
Push 1
st
time
Outdoor capacity
Push 2
nd
time
Digital comp loading time
Push 3
nd
time
High pressure (kg/cm
th
Push 4
time
Low pressure (kg/cm
Push 5
th
time
Discharge temperature of compressor 1
th
Push 6
time
Discharge temperature of compressor 2
Push 7
th
time
Discharge temperature of compressor 3
th
Push 8
time
CT sensor value of compressor 1
Push 9
th
time
CT sensor value of compressor 2
th
Push 10
time
CT sensor value of compressor 3
th
Push 11
time
Suction temperature
th
Push 12
time
Cond_out temperature
th
Push 13
time
Liquid tube temperature
th
Push 14
time
Oil temperature sensor on oil balancing pipe
th
Push 15
time
Sump temperature of compressor 1
th
Push 16
time
Ambient air temperature
th
Push 17
time
EVI_in temperature
th
Push 18
time
EVI_out temperature
th
Push 19
time
Main EEV1 step
th
Push 20
time
Main EEV2 step
th
Push 21
time
EVI EEV step
th
Push 22
time
HR EEV step
th
Push 23
time
Fan step ( SSR or BLDC )
th
Push 24
time
Version
Page 31
SEG 1 SEG 2
SEG 3 SEG 4
Key function
2
)
2
)
Note : LED display alphabet
Display LED
SEG 1
Ex) 16 HP ➞ Off, 1, 6
1
Ex) Loading 13 sec ➞ Off, 1, 3
2
3
Ex) High pressure 15.2 (kg/cm
4
Ex) Low pressure 4.3 (kg/cm
Ex) 87˚C ➞ 0, 8, 7
5
Ex) 87˚C ➞ 0, 8, 7
6
Ex) 87˚C ➞ 0, 8, 7
7
8
9
A
Ex) -5 ˚C ➞ -, 0, 5
B
Ex) 35 ˚C ➞ 0, 3, 5
C
Ex) 35 ˚C ➞ 0, 3, 5
D
Ex) 35 ˚C ➞ 0, 3, 5
E
Ex) 35˚C ➞ 0, 3, 5
F
Ex) 35˚C ➞ 0, 3, 5
G
Ex) 35˚C ➞ 0, 3, 5
H
Ex) 35˚C ➞ 0, 3, 5
I
Ex) 2000 steps ➞ 2, 0, 0
J
Ex) 2000 steps ➞ 2, 0, 0
K
Ex) 300 steps ➞ 3, 0, 0
L
Ex) 300 steps ➞ 3, 0, 0
M
Ex) 13 steps ➞ Off, 1, 3
N
SEG 2, 3, 4
) ➞ 1, 5, 2
2
) ➞ 0, 4, 3
2
Ex) 2A ➞ 0, 0, 2
Ex) 2A ➞ 0, 0, 2
Ex) 2A ➞ 0, 0, 2
VI-31