operating instructions
Aeration
Adjustment
The air shutter can be adjusted by moving the
adjusting wire up or down. The wire is accessed
through the bottom louver opening. Open the air
shutter for a blue flame or close for a yellower
flame. The burner aeration is factory set but may
need adjusting due to either the local gas supply
or altitude.
Minimum Air Shutter Opening:
3/16"
Natural Gas
3/8"
Propane
CAUTION: Carbon will be produced if air shutter
is closed too much.
Note: Any damage due to carboning
resulting from improperly setting
the aeration controls is NOT
covered under warranty.
Adjustment Wire - Push to close or
pull to open aeration cap.
Closed - Tall yellow
Open - Short Blue
Note: Aeration Adjustment should only
be performed by an authorized
Regency
Installer at the time of
®
installation or service.
|