Regency Panorama P121E-NG11 Owners & Installation Manual page 29

Zero clearance direct vent gas fireplace
Table of Contents

Advertisement

Vertical Venting with Two (2) 90
Option
V + V1
A)
1' (305mm) Minimum
B)
2' (610mm) Minimum
C)
3' (914mm) Minimum
D)
4' (1.22m) Minimum
E)
5' (1.52m) Minimum
F)
6' (1.83m) Minimum
With the above options, maximum total pipe length if 37 feet with
minimum of 6 feet total vertical and maximum 17 feet total horizontal.
Please note minimum 1 foot between 90
Diagram 9
Vertical Venting with Three (3) 90
Elbows
o
H
4' (1.22m) Maximum
6' (1.83m) Maximum
9' (2.74m) Maximum
12' (3.66m) Maximum
15' (4.57m) Maximum
17' (5.18m) Maximum
o
elbows is required.
Elbows
o
Option
A)
B)
C)
D)
With the above options, maximum total pipe length if 37 feet with
minimum of 5 feet total vertical and maximum 12 feet total horizontal.
Please note minimum 1 foot between 90
Diagram 11
Vertical Venting with Two (2) 90
Option
V
A)
1' (305mm) Minimum
B)
2' (610mm) Minimum
C)
3' (914mm) Minimum
D)
4' (1.22m) Minimum
With the above options, maximum total pipe length if 37 feet with
minimum of 4 feet total vertical and maximum 8 feet total horizontal.
Please note minimum 1 foot between 90
Diagram 10
V + V1
2' (610mm) Min. 1' (305mm) Max. 2' (610mm) Max.
3' (914mm) Min. 4' (1.22m) Max. 5' (1.5m) Max.
4' (1.22mm) Min. 6' (1.86m) Max. 8' (2.4m) Max.
5' (1.5m) Min.
8' (2.4m) Max.
Regency
P121E-11/P131E-11 Zero Clearance Direct Vent Gas Fireplace
®
installation
Elbows
o
H + H1
2' (610mm) Maximum
4' (1.22m) Maximum
6' (1.83m) Maximum
8' (2.44m) Maximum
elbows is required.
o
H
H + H1
12' (3.6m) Max.
elbows is required.
o
|
29