Errors; View Errors; Diagnose Errors - Graco PrecisionSwirl Instructions-Parts List Manual

Precision dispense system
Table of Contents

Advertisement

Errors

Errors

View Errors

When an error occurs, an error pop-up is displayed that
takes up the entire screen until the error is
acknowledged by pressing
acknowledged over the gateway. Active errors are
displayed in the menu bar.
Error
F
. 43: Error Pop-Up
IG
The previous 200 errors are displayed on the error
report screens. See Run Mode, page 116, for
instructions on navigating to and through the error report
screens.
There are three levels of errors: alarms, deviations, and
advisories. Alarms cause the system to shut down.
Deviations and advisories do not shut down the system.
NOTE:
Alarms set the dispenser (fluid plate) ready signal
LOW.
Advisories and deviations do not set the dispenser
(fluid plate) ready signal LOW.
Errors can be viewed through a CGM on models that do
not have an ADM. See Appendix C, page 128, Output
bits 0x0DB. The Error codes are described by a 4 digit
ASCII string. For example: the first event code in the
manual is EC0X and is represented using an ASCII
table:
E = 0x45
C = 0x43
0 = 0x00
X = 0x58
70
. Errors can also be

Diagnose Errors

See Event and Error Codes and Troubleshooting on
page 71 for error codes, possible causes, and solutions.