Appendix C - Communications Gateway Module (CGM) Connection Details

Appendix C - Communications Gateway Module
(CGM) Connection Details

Install Fieldbus Connections

Connect cables to fieldbus per fieldbus standards.
PROFINET
NS
F
. 72: PROFINET Fieldbus Connections
IG
The Ethernet interface operates at 100Mbit, full duplex,
as required by PROFINET. The Ethernet interface is
auto-polarity sensing and auto-crossover capable.
Network Status (NS)
State
Description
Off
Offline
Green
On-line,
(RUN)
Flashing
On-line,
Green
(STOP)
128
MS
Link
TI11814A
Comments
No power
No connection with IO
Controller
Connection with IO Con-
troller established
IO Controller with RUN
state
Connection with IO Con-
troller established
IO Controller in STOP
state
Module Status (MS)
State
Description
Off
Not initial-
ized
Green
Normal
operation
Flashing
Initialized,
Green
diagnostic
event(s)
present
Red
Exception
error
Red (1
Configura-
flash)
tion error
Red (2
IP Address
flashes)
not set
Red (3
Station
flashes)
Name not
set
Red (4
Major Inter-
flashes)
nal Error
Link/Activity (Link)
State
Off
No Link, no communication present
Green
Link established, no communication present
Green,
Link established, communication present
flashing
Comments
No power or module in
"SETUP" or "NW_INIT" state
Diagnostic event(s) present
Used by engineering tools to
identify node on network
Module in state "EXCEPTION"
Expected Identification differs
from Real Identification
Set IP address via system
monitor or DNS server
Set Station Name via system
monitor
Cycle system power; replace
module
Description