LG PRCKD42E Owner's Manual page 95

Ahu control kit
Table of Contents

Advertisement

2. Cooling (Heating) Ventilation Temperature/Humidity Settings
① Temperature Settings
① Temperature Settings
The default cooling/heating temperature is 18.0 °C/16.0 °C, and it can be adjusted at an in-
crement/decrement of 0.1 °C between 18.0 °C/16.0 °C and 30.0 °C
Temperature (humidity) cannot be set in the following cases.
- When the AHU ventilation temperature/humidity sensors are not installed in Administrator
Settings 2.
A warning message will appear if the temperature is outside the range, in which case you
need to re-enter the value.
② Humidity Settings
The default cooling/heating humidity is 50%, and it can be adjusted at an increment/decre-
ment of 1%RH between the range of 30~80%RH.
Humidity (ventilation) cannot be set in the following cases.
- If the ventilation/humidity sensor is not set.
A warning message will appear if the humidity is outside the range, in which case you
need to re-enter the value.
② Humidity Settings
① Enter the desired input value by using
② Enter the value and then click the 'OK'
HMI SETTING
the key button.
button to enter the input value.
95

Advertisement

Table of Contents
loading

Table of Contents