Fan Motor Driver Module Capacity Settings
- The induction motor capacity is determined by whether the CN_TH1 connector pin is inserted in
the driver module. The motor can be started without a problem by configuring the settings ac-
cording to the capacity.
- Configure the motor settings and capacity by connector pin type in accordance with the table
below.
!
CAUTION
• The connector pins must be distinguished clearly according to the capacity in order for the
product to function properly.
• The motor can create an abnormal noise if the connector pins are not set properly. It can
also cause vibration and damage to the product.
• Make sure to check if the capacity was set properly before connecting the power supply.
FAN DRIVER MODULE CONNECTION
- Motor and Capacity Classification
Motor
Capacity
Classification
Classification
3.7 KW
Induction
Motor
2.2 KW
Capacity Settings Connector
39
Connector Pin
CN_TH1
Not Inserted
Inserted
CN_TH1

Advertisement