LG PRCKD42E Owner's Manual page 104

Ahu control kit
Table of Contents

Advertisement

HMI SETTING
104
5. Set the Temperature-Based Wind Speed
The frequency is determined by the difference between the desired and current temperature,
and the control cycle and setting steps are as follows.
- Ventilation/Supply 30~60Hz Can be Set, Default Value: 50Hz
- Control Cycle 1~60 Min.
- Selection Step: 1~5Hz
- Set Supply/Ventilation (High)
The default high speed wind is 50 Hz, and it can be adjusted within 30。and 90 Hz.
- Set Supply/Ventilation (Medium)
The default medium wind speed is 50 Hz, and it can be adjusted within 30~60 Hz.
- Set the Supply/Ventilation (Low)
The default low wind speed is 30 Hz, and it can be adjusted within 30~60 Hz.
※A warning message will appear if a value outside the temperature range is entered, in which
case you can re-enter the value within the range.
① Click the box to open a screen where the
setting can be set/entered.
② Enter the desired input value by using
the key button.
③ Enter the value and then click the 'OK'
button to enter the input value.