3) Enter the Ventilation/Supply Flow Range
- The lowest default flow is 0.0 m/s and the input range is 0.0~20.0 m/s, which can be ad-
justed at an increment/decrement of 0.1 m/s.
- The highest default flow is 20.0 m/s and the input range is 0.0~20.0 m/s, which can be ad-
justed at an increment/decrement of 0.1 m/s.
h A warning message will appear if a value outside the designated range is entered, in which
case you can re-enter the value within the range.
The highest setting value cannot be lower than the lowest setting value, and the highest
value must be at least 4.9 m/s higher than the lowest value in the settings. By the same
token, the lowest value must be at least 4.9 m/s lower than the highest value.
A warning message will appear if the difference is less than 49 m/s, in which case you
need to re-enter the value within the designated range.
4) CO
Sensor Range Input
2
- The lowest default CO
increment/decrement of 10 PPM.
- The highest default CO
at an increment/decrement of 10 PPM.
※ A warning message will appear if a value outside the designated range is entered, in
which case you can re-enter the value within the range.
5) Heat Source Temperature Range Settings
- The lowest default heat source for cooling/heating is 12.0 °C/40.0 °C, and the temperature
can be entered between 10.0/30.0~20.0/45.0 °C at an increment/decrement of 0.1 °C.
- The highest default heat source for cooling/heating is 18.0 °C/50.0 °C, and the temperature
can be entered between 10.0/35.0~25.0/45.0 °C at an increment/decrement of 0.1 °C.
h A warning message will appear if a value outside the temperature range is entered, in
which case you can re-enter the value within the range. The highest temperature cannot
be lower than the lowest temperature, and the highest temperature must be at least
1.9 °C higher than the lowest temperature in the settings. By the same token, the lowest
temperature must be at least 1.9 °C lower than the highest temperature.
A warning message will appear if the temperature difference is less than 1.9 °C, in which
case you need to re-enter the temperature within the designated range.
level is 0 PPM, and the level can be set between 0~990 PPM at an
2
level is 0 PPM, and the level can be set between 1000~2000 PPM
2