INSTALLATION LAYOUT

Installation composition diagram
No.
¿
Air handling unit
¡
¬
Expansion kit unit
ƒ
Pipe Temperature Sensor IN
Pipe Temperature Sensor OUT
∆ -
1, 2
Temperature/humidity sensor RA, SA
«-
1, 2
Ventilation Fan, Supply Fan
» -
1, 2
Ventilation, Supply Driver KIT
Caution on installation layout
- MCC is part of the installation construction to be performed by the equipment supplier, so con-
fer with the supplier before installing the product.
- Temperature/humidity sensors must be installed on the SA (supply)/RA(ventilation) ducts before
the product can run normally.
Item
Control kit
Outdoor unit
MCC
INSTALLATION LAYOUT
Power cable
Communication cable
Pipe sensor
Temperature/
humidity sensor
Refrigerant hose
Applied Standards
-
PRCKD42
PATX13A0/20A0/25A0/35A0
MULTI V
Sensor: Ø 5, Length: 10m, Color: Black
Sensor: Ø 7, Length: 10m, Color: Red
-40 °C ~ 70 °C, RH 0 ~ 95 %/AC 24 V/DC 0 ~ 10 V
-
1 Driver KIT can be connected to 2 Fans
MCC Switchboard Panel