Address Switch; Function Switch; Seven-Segment Display - Delta AH500 Manual

Hide thumbs Also See for AH500:
Table of Contents

Advertisement

AH 5 00 Mo d u le Ma n ua l

10.2.4 Address Switch

The switch is used on setting up the node address of AH10DNET-5A on DeviceNet. Range: 00~63
(64~99 are forbidden.)
Switch setting
0-63
64-99
Example: If you need to set the node address of AH10DNET-5A to 26, simply switch the
corresponding switch of x10
Note:
1. After the setup is completed, repower AH10DNET-5A. While AH10DNET-5A is working,
changing the setting of node address will be invalid.
2. Use the slotted screwdriver to rotate the switch carefully in case you scratch the switch.

10.2.5 Function Switch

The function switches are used for:
Setting up the work mode (IN0)
Setting up the baud rate of DeviceNet (DR0~DR1)
DR1
DR0
Baud rate
OFF
OFF
125 kbps
OFF
ON
250 kbps
ON
OFF
500 kbps
Entering the mode of extended baud rate (See
ON
ON
section 10.7.3.)
When the corresponding equipment is off-line,
ON
the I/O data in the buffer area will be held.
IN0
When the corresponding equipment is off-line,
OFF
the I/O data in the buffer area will be cleared.
IN1
Reserved
Note:
1. After the setup of the function switch including DR1, DR0 and IN0 is completed, repower
AH10DNET-5A.
2. Use slotted screwdriver to adjust the DIP switch carefully in case you scratch the switch.

10.2.6 Seven-segment Display

The digital display provides the following function:
Showing the node station number of AH10DNET-5A
Showing the error message of the slave
Note:
1. While AH10DNET-5A is working normally, the digital display shows its own node address.
2. If "E1" and "03" are shown continuously, it indicates that the error of E1 exists in the slave of
node address 03.
3. If the error codes such as "E7" and "E1" are shown, please refer to section 10.10.2 for
treatment.
10.2.7 Backplane Interface
The interface is used for connection between AH10DNET-5A and a backplane.
1 0 - 6
Description
Valid DeviceNet node address
Invalid DeviceNet node address
1
to 2 and the corresponding switch of x10
Max. transmission distance
500 m
250 m
100 m
0
to 6.